SolConeX Wall-mounting socket, 125 A
Series 8581/31
7.3
Installation
DANGER
Explosion hazard due to insufficient protective measures!
Non-compliance results in severe or fatal injuries.
• Select suitable cables to ensure that the maximum permissible
conductor temperatures are not exceeded.
• Lay cables in intrinsically safe circuit separately to cables in
non-intrinsically-safe circuits. The distance measurements for this
can be found in the "Separating intrinsically safe circuits from
non-intrinsically-safe circuits" section.
• When using core end sleeves, attach them using a suitable tool.
• Use only separately tested cable entries and stopping plugs with
an EU Type Examination Certificate.
• The conductor insulation must be touching the terminal.
• Do not damage the conductor (e.g. nicking) when stripping it.
• Always connect the protective conductor.
DANGER
Explosion hazard in the case of installation in special areas with
potentially explosive dust!
Non-compliance results in severe or fatal injuries.
• Do not use the device in areas where there are processes
generating strong charges, machine friction processes,
separation processes and electrospray processes
(e.g. around electrostatic coating systems) and
pneumatically generated dust.
DANGER
Explosion hazard when seal is insufficient and/or service temperature
is too high!
Non-compliance results in severe or fatal injuries.
• Completely seal the bayonet ring of the plug and of the hinged
cover to obtain the degree of protection.
• Securely seal and lock the enclosure.
• Make sure the service temperature range is maintained
(see the "Technical data" chapter).