Mounting and Installation
16
205582 / 8581615300
2020-08-27·BA00·III·en·05
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
SolConeX Wall-mounting socket, 125 A
Series 8581/31
Auxiliary contacts in Ex i circuits
If the auxiliary contacts of Type 8080/1 are used in Ex i circuits, they must be provided
with a covering (Art. No. 169683).
Mounting Ex i covering for auxiliary contacts
12436E00
• Insert the covering (4) onto the auxiliary contact from the top until it snaps into place
in the lug.
The customer is only allowed to install an intrinsically safe auxiliary contact if
no pick-off terminal blocks are mounted on the two terminals located on the
left and right side of the installation slot used!
The Ex i covering serves to ensure the required tight string length (50 mm)
between the connection points of intrinsically safe and non-intrinsically
safe circuits.