Error and warning signals, faults

 
10.2013 

B

A

_S

LE

22

_E

N

.D

O

C

X

 

8

 

Error and warning signals, 

 

 

 

 

 

 

8.1

 

Operation 

 

III 

II 

err 

pwr 

Cause 

 

 

 

 

 

Device is ready for use

8.2

 

Error status signals 

 

III 

II 

err 

pwr 

Cause 

 

 

 

 

 

Sensor error:

cable break
short circuit

 

 

 

 

 

Overload

 

 

 

 

 

Overtemperature

 

 

 

 

 

Lifting and lowering 
activated simultan
ously 

 

 

 

 

 

Internal error

 

 

 

 

 

Sensor erro

Difference between two 
load sensor channels is 
too high 

 

 

 

 

 

No supply present, 
device fuse faulty 

Error and warning signals, faults 

 

Error and warning signals, faults 

 

 DANGER 

 

The electrical installation may only be checked by a 

skilled electrician

 
Only a 

qualified person

 may alter the overload cut-off point or replace the device.

 
 

A detailed description of errors can be found in the "Service instructions of the 
original operating instructions". 

 
Internal tests are performed when the supply voltage is switched on. 
"err", "I", "II", "IIII" are illuminated. 
The SLE22 is ready for use when only the "pwr" LED is still 
 
Symbols 

 LED off               

 LED flashes                 

 LED 

 

Consequence 

Elimination

Device is ready for use 

 

 

 

The SLE22 is continuously performing internal tests, tests of the sensors connected and 
plausibility monitoring of external and internal switching status. 
problem, an error or error status is set and lifting or lifting and lowering a
 
The errors possible and their display are described in the following table and must be 
eliminated to continue operation. 
 

Conse-
quence 

Elimination 

Sensor error: 

cable break,  
short circuit 

Lifting dis-
abled 

Check electrical connection of load sensors.
 

Overload

 

Lifting dis-
abled 

 

Set down overload 

 

If necessary correct cut
missioning)  

Overtemperature1

 

Lifting and 
lowering 
disabled 

 

Allow hoist motor to cool down

 

Replace PTC thermistors

Lifting and lowering 
activated simultane-

Lifting and 
lowering 
disabled 

Faulty wiring. Check 

activation

Internal error

 

Lifting and 
lowering 
disabled 

Reboot device 
check voltage at terminal 6

Sensor error 

Difference between two 
load sensor channels is 

  

Lifting dis-
abled 

Check electrical connection of load sensors.
 

Acknowledgement only by rebooting device!

No supply present, 
device fuse faulty  

Device not 
functioning. 

Check supply voltage of device

 

 

23 

skilled electrician

off point or replace the device. 

"Service instructions of the 

Internal tests are performed when the supply voltage is switched on. The LEDs "pwr", 

The SLE22 is ready for use when only the "pwr" LED is still illuminated. 

LED on 

Elimination 

The SLE22 is continuously performing internal tests, tests of the sensors connected and 
plausibility monitoring of external and internal switching status. If the SLE22 detects a 
problem, an error or error status is set and lifting or lifting and lowering are disabled. 

The errors possible and their display are described in the following table and must be 

Check electrical connection of load sensors. 

 

If necessary correct cut-off threshold (during com-

Allow hoist motor to cool down 
Replace PTC thermistors 

activation

check voltage at terminal 6 

Check electrical connection of load sensors. 

Acknowledgement only by rebooting device!

 

supply voltage of device. 

Содержание SLE22

Страница 1: ...SLE22 Translation of Original Operating Instructions...

Страница 2: ...plified circuit diagram 10 3 6 Safety functions 11 3 6 1 Overload cut off 11 3 6 2 Sensor errors 11 3 7 General functions 12 3 7 1 Activation relay outputs and motor management 12 3 7 2 Mechanical ope...

Страница 3: ...rating instructions for wire rope hoists chain hoists and in chapter 4 8 Electrical equipment further important information and explanations which must be ob served 1 2 Contents of operating instructi...

Страница 4: ...esulting in death CAUTION This symbol gives warning of situations which are potentially dangerous to health Ignoring these warning notices may lead to injuries NOTICE warns of damage to property or th...

Страница 5: ...tion with the application Qualified persons with the competence to undertake certain mainte nance work on our products include the manufacturer s service engineers and trained fitters with the corresp...

Страница 6: ...compliance with EN13849 1 2006 is a configurable system that performs its safety functions only after the safety relevant parameter overload cut off point has been set which may be altered by a quali...

Страница 7: ...cable must be shielded The shield is connected to the ground close to the device ideally directly next to the device If there is an intermediate terminal on the load sensor lead connect the shield is...

Страница 8: ...ure of one of the downstream power devices Downstream power devices are not monitored by the SLE22 Failure must be prevented by the designer of the control selecting appropriate devices If a device fa...

Страница 9: ...tegral part of the prototype test of the device and is thus a safety relevant component For this reason only load sensors approved by the manufacturer must be used If a load sensor is defective the sa...

Страница 10: ...3 Safety input up S 4 Safety input down S 5 Input fast S Relay outputs 6 Switching voltage of relays L 7 Safety output slow up K 8 Safety output fast up K 9 Safety output slow down K 10 Safety output...

Страница 11: ...less than 82 5 of maximum working load and safety input S is active for 2 seconds or the load minimum load corresponds to a current value of 6 mA for 2 seconds Outputs K and K can be switched after a...

Страница 12: ...an internal safe circuit In the case of a fault or at overload this circuit discon nects safety outputs K and K Safety outputs K and K are also supplied by an internal safe circuit in accordance with...

Страница 13: ...3 General description function 10 2013 13 BA_SLE22_EN DOCX If the direction of activation is reversed the hoist is stopped and the relevant safety output is activated after cut off time tr has expired...

Страница 14: ...d cut off times is set via switch S1 and DIP switch S3_1 DANGER Alterations to the settings of S1 and S3_1 may only be performed by a qualified person Motor management table This table shows the corre...

Страница 15: ...ance measured at the ptc thermistor input drops to 80 Ohm a ptc thermistor error is displayed for 1 and the hoist motions disabled as for overtemperature see chapter 9 2 1 WARNING 2 The travel motor P...

Страница 16: ...ion S3_7 off S3_7 on err S3_6 off S3_6 on Err switches at every error condition which interrupts a hoist motion Option can be parameterized as required Parameterizing is dependent on the position of s...

Страница 17: ...n must be performed by a skilled electrician The maximum values for tighten ing torques given in EN ISO 898 1 must be observed for all screws All screws must be checked for firmness and tightened if n...

Страница 18: ...met when using the SLE22 and that correct functioning of the components or units affecting the safety function in interaction with the SLE22 is ensured In addition the type of use mounting of the SLE2...

Страница 19: ...Activating Crane test function Preparations before activating crane test remove lid with a screwdriver hexagon socket width across flats 2 5 The Crane test function can only be activated when the hoi...

Страница 20: ...ew cut off point it must be documented confirmed and signed in the lid of the case in the following table and in the crane logbook Any undocumented alteration of the cut off point leads to an immediat...

Страница 21: ...on the front of the device These can be seen from Chapter 8 Error and warning signals faults The device is ready for operation after commissioning by a qualified person The device must be recommission...

Страница 22: ...t have the following characteristics Identical or higher hardware status Identical or higher software status Identical or higher temperature range These characteristics can be seen from the rating pla...

Страница 23: ...short circuit Lifting dis abled Check electrical connection of load sensors Overload Lifting dis abled Set down overload If necessary correct cut missioning Overtemperature1 Lifting and lowering disa...

Страница 24: ...restart activation Overtemperature2 pause and allow motor s to cool down usually the DC has been exceeded at the same time use forced ventilation if warning continues although motor is cold then check...

Страница 25: ...must be avoided Replacement and recommissioning the SLE22 must be performed by a qualified person See Chapter 4 4 Replacement of device and sensor Disposal of the device must comply with national envi...

Страница 26: ...l free contacts yes Analog safety inputs Number 2 Measuring range 0mA 25 5 mA Max measurement error at 25 C related to minimum cut off point of 13 0 mAM 3 Limit frequency 20 Hz Input impedance 39 2 Oh...

Страница 27: ...aptive plus minus screws tightening torque 0 5 Nm per box terminal 1 x 4 mm2 solid or 1 x 2 5 stranded wire with sleeve DIN 46 228 or 2 x 1 5 mm2 stranded wire with sleeve DIN 46 228 Attachment Top ha...

Страница 28: ...late for countries with UL and CSA approval requirements Part number Supply voltage 579 572 0 230 V AC 50 60 Hz 579 574 0 48 V AC 50 60 Hz 579 575 0 42 V AC 50 60 Hz 579 576 0 24 V DC 579 577 0 24 V A...

Страница 29: ...66083015 infochina stahlcranes com India Chennai Tel 91 44 43523955 Fax 91 44 43523957 infoindia stahlcranes com Spain Madrid Tel 34 91 4840865 Fax 34 91 4905143 infospain stahlcranes com France Pari...

Отзывы: