Operating Instructions ET-xx8 / MT-xx8
Appendix B
Page 62 of 84
R. STAHL HMI Systems GmbH / OI_ET_MT-xx8_en_V_01_02_03.docx / 10.03.2021
18.6 Non intrinsically safe interfaces (Ex e)
18.6.1
X1
– Power supply
Nominal voltage
Device version AC
=
100 … 240
VAC
Device version DC
=
20 … 30
VDC
Nominal current
Device version AC
=
Max. 5
A
Device version DC
=
Max. 8
A
Nominal power
=
150
W
Max. input voltage
U
m
=
250
VAC
Frequency for AC
=
50
– 60
Hz
18.6.2
X2 / X3
– copper1 / copper2
Nominal voltage
=
5
VAC / VDC
Max. input voltage
U
m
=
250
VAC
18.6.3
X4
– DC out
Nominal voltage terminal 1
=
12
VDC
Nominal voltage terminal 4
24
VDC
Max. input voltage
U
m
=
250
VAC
18.6.4
X5
– CAN
Nominal voltage
=
5
VAC / VDC
Max. input voltage
U
m
=
250
VAC
18.6.5
X6
– USB
Nominal voltage
=
5
VAC / VDC
Max. input voltage
U
m
=
250
VAC
18.6.6
X7
– RSxxx
Nominal voltage
=
12
VAC / VDC
Max. input voltage
U
m
=
250
VAC
18.6.7
X8
Not in use !
Do not connect anything !
18.6.8
X9
– Audio / Video
Nominal voltage
=
5
VAC / VDC
Max. input voltage
U
m
=
250
VAC
18.6.9
X10
– SATA
Nominal voltage
=
5
VAC / VDC
Max. input voltage
U
m
=
250
VAC
NOTE