Appendix A
Operating Instructions ET-xx8 / MT-xx8
R. STAHL HMI Systems GmbH / OI_ET_MT-xx8_en_V_01_02_03.docx / 10.03.2021
Page 55 of 84
17.2.3
Interfaces
Function / Equipment
ET-438
MT-438
ET-498
MT-498
ET-538
MT-538
ET-598
MT-598
Ethernet note
Either TX, 2TX or 2FX
Ethernet / Data
1x 100/1000Base-TX (Ex e)
2x 100/1000Base-TX (Ex e)
2x 100Base-FX (Ex op is)
Copper TX
Data cable
CAT7 installation cable AWG 23
Length of data
cable
max. 100 m
Interface medium
CAT7 Data transmission
Fibre optic FX Data cable
FO cable 50/125 μm or 62.5/125 μm
Length of data
cable
max. 5000 m (for core cross section 50 and use of 9721/13-11-14)
max. 4000 m (for core cross section 62.5 and use of 9721/13-11-14)
Interface medium
multi-mode optical fibre cable
USB interface
3x USB (Ex ia)
1x USB (Ex e)
Serial interface
1x RS-232 / RS-422 / RS-485 (Ex e)
Optional interface 1
WLAN 2.4 GHz (Ex i)
WLAN 5 GHz (Ex i)
Standard 802.11 abgn
Audio interface
1x Audio line out (Ex e) (only with AMD)
Interface reader
1x reader / barcode reader interface (Ex i)
WLAN
optional (only together with 1x 100/1000Base-TX)
Bluetooth
Standard
Front camera
optional, 5 megapixels, in-built
Further connections
12 / 24 V DC output
2x Fan
On/off switch
Plug version FO
SC duplex socket
17.3 Additional data for SERIES 600 KVM Systems
17.3.1
General
Function / Equipment
ET-638
MT-638
ET-698
MT-698
Technology
KVM System
17.3.2
Electrical data
Function / Equipment
ET-638
MT-638
ET-698
MT-698
Transfer Technology
KVM-DVI3
operating system
independent
Language support
User menu: English