Operating Instructions MT-xx6-A
Operation
Page 34 of 60
R. STAHL HMI Systems GmbH / OI_MT_xx6_A_en_V_03_00_26.docx / 03.11.2020
X8
0
+U_INT1
Reader interface
1
0V
Ex ib/ic
2
+U_EX1
3
GND
4
+U_RD
5
Signal 1
6
Signal 2
7
Signal 3
8
Signal 4
9
+U_EX1 (out)
X9
1
VCC
PS2 interface *
2
KBDAT
Ex ib/ic
3
KBCLK
for
4
MSDAT
external keyboard /
5
MSCLK
mouse
6
GND
X10
1
Optical fiber connection type duplex SC - female
Ethernet optical
fiber interface **
X11
1
TxD (+)
Ethernet copper
2
TxD (-)
Connection **
3
RxD (+)
4
RxD (-)
The COM interface may only be wired as a RS-232 or as a RS-
422/485 connection !
Simultaneous wiring of the RS-232 and RS-422/485 interface is not
allowed !
* Do
NOT
connect the optional external keyboard to live equipment !
** Please note that the Ethernet connection is either for an optical
fibre connection (X10) or for a copper connection (X11),
depending on the version ordered !
The optical fiber connection requires a multimode optical fiber
cable with 62.5 µm core diameter and 125 µm external diameter.
Copper wires with cross sections of between 0.2 mm² (AWG24)
and 2.5 mm² (AWG14) may be connected to any of the terminals
of the HMI devices.
Which cable cross sections are chosen should be decided on the
basis of relevant regulations, such as DIN VDE 0298. Factors that
might require a larger cross section, such as current, increased
temperatures, cable bundling, etc. must also be taken into
account !
NOTICE