Operating Instructions MT-xx6-A
Permitted maximum values
Page 18 of 60
R. STAHL HMI Systems GmbH / OI_MT_xx6_A_en_V_03_00_26.docx / 03.11.2020
7.1.3.1
Tightening torque
For the terminals X1 and X11 a tightening torque of:
0.4 Nm up to 0.5 Nm is valid
and for the terminals X2, X3, X4, X5, X6, X7, X8 and X9 a tightening torque of:
0.5 Nm bis 0.6 Nm is valid.
The stipulated tightening torques of the connection terminals must be
observed and applied. Again, they must be checked and possibly
adjusted before commissioning !
8
Permitted maximum values
8.1
External, non-intrinsically safe circuits
Input voltage (X1):
Rated voltage
24 VDC (+20 % / -15 %)
(for exclusive operation in zone 2)
Power consumption for U
rated
1.5 A max
Max. operating voltage U
m
30 VDC
(applies for connected circuits in zone 1)
RS-422/-232 COM 1 (X2):
Rated voltage
RS-422: 5 VDC
RS-232: ±12 VDC
Max. operating voltage U
m
253 VAC
USB-1 (X5):
Rated voltage
5 VDC
Max. operating voltage U
m
253 VAC
USB-3 (X7):
Rated voltage
5 VDC
Max. operating voltage U
m
253 VAC
Copper Ethernet (X11):
Rated voltage
5 VDC
Rated power
100 mW
Max. operating voltage U
m
30 VDC
Audio (X3)
Rated voltage
5 VDC
Max. operating voltage U
m
253 VAC
8.2
External inherently safe optical interface
Ethernet optical fiber (X10):
Wavelength
1350 nm
Radiant power
≤ 35 mW
NOTICE