Frequency Transmitter
Field Circuit Ex i
Series 9146
9.2.7 Start Override
The start override ensures that the limit value settings "On below limit value" or
"Off below limit value" do not activate the limit value contact even if the value has fallen
below the limit value. This function allows a machine or system start without an alarm
message being output.
When the anti-pumping device is active, the first edge at input ensures the start of the
function. A reactivation is made possible by briefly interrupting the power supply.
10
Operation
10.1 Operation
Possible adjustments during operation
For a detailed description of the function of the DIP switches and the possible
adjustments using the "ISpac Wizard" software, refer to chapter "Parameterization and
commissioning".
10.2 Indications
The corresponding LEDs on the device indicate the operating state of the device
(see also the "Function and device design" section).
Changing the adjustments for the different operating modes or the line fault
detection via the "ISpac Wizard" software or the DIP switches is also
permitted during operation in Zone 2 and with connected intrinsically
safe input signals.
LED
Colour LED "ON"
LED "OFF"
"PWR" LED
green
Device is supplied with auxiliary power Device is not in operation, power
supply not available
"LF1" LED
red
Line fault in signal of channel 1
No line fault in signal of channel 1
"LF2" LED
red
Line fault in signal of channel 2
No line fault in signal of channel 2
"A" LED
yellow Limiting value A exceeded or
undershot.
Limit contact has switched.
Limiting value A not exceeded or
undershot.
Limit contact is in the rest position.
"B" LED
yellow Limiting value B exceeded or
undershot.
Limit contact has switched.
Limiting value B not exceeded or
undershot.
Limit contact is in the rest position.