CPU & Power Module
Type 9440/15-01-11
9440 6 031 002 1
2016
03.03. Bagusch
Kaiser
1 of 1
Class I, DIV 2 / Zone 2 Installation
for connection to I/O Modules located in
Class I, II, III, Division 2, Group A-G,
or Class I, Zone 2, Group IIC/IIB
Hazardous (Classified) Locations
Connection allocation
CPU & Power Module for Division 2 or Zone 2, type 9440/15-01-11
X3
X2
X1
X5
Power supply (X5)
Description
Function
Connector
number
Terminal
3-pin name
24 V DC (+)
0 V
Ground
X5
X5
X5
L+
L-
GND
Fieldbus (X1, X2) and Service Bus (X3)
Description
Function
Connector
number
Sub-D 9 pin
number
Data B (+)
Reference potential for
the interface
(out of the equipment)
Supply voltage
(out of the equipment)
Data A (-)
-
RxD/TxD (+)
GND
5 V (+)
RxD/TxD (-)
Not connected
X1, X2, X3
X1, X2, X3
X1, X2, X3
X1, X2, X3
X1, X2, X3
3
5
6
8
1,2,4,7
The Type 9440/15-01-11 CPU & Power Module is an nonincendive
module for installation in Class I, Division 2, Group A-D or Class I,
Zone 2, Group IIC/IIB hazardous location; Providing intrinsically safe
BusRail and nonincendive RS485 interfaces according to NEC Article
504/505 or Canadian Electrical Code, CSA C22.
Safety data for wiring configurations to the left are as follows:
Power Supply (input/primary)
Connector X5
U
in
= 24 V DC (20 V … 35 V DC)
I
in
= 5.2 A
U
max
= 250 V
Data interfaces RS 485
(primary)
Connectors X1, X2, X3
Data circuits as per I/O Standard
RS 485
V
max
= 250 V
Nonincendive connections
V
OC
= 13.2 V, I
SC
= 110 mA
C
i
= 0.12 µF, L
i
= 0 mH
U
max
= 13.2 V, I
max
= 110 mA
C
a
= 5 µF, L
a
= 6.5 mH
Module 1-16 over BusRail:
CL I, DIV 1, A-D / CL I Zone 1, GP IIC/IIB:
Power Supply (output/secondary):
With intrinsically safe type of protection:
Maximum value:
V
OC
= 26.2 V
The circuit requires external current limitation which is provided by the
system
Address and data bus (secondary):
With intrinsically safe type of protection:
Maximum values: V
OC
= 6.6 V
I
SC
= 105 mA
V
max
= 6.6 V
Linear characteristic curve, the effective internal capacitance and
inductance are negligibly small.
Notes:
1.
For Entity concept use the appropriate parameters from above to
ensure the following:
V
OC
or V
t
V
max
C
a
C
i
+ C
leads
I
SC
or I
t
I
max
L
a
L
i
+ L
leads
2.
Electrical Apparatus connected to an intrinsically safe system
must not use or generate voltages > 250 V (Umax)
3.
Do not connect or disconnect non I.S. power supply to X5 unless
area is known to be non-hazardous.
4.
Do not detach from or plug the CPU & Power Module to the
BusRail when energized, unless area is known to be non-
hazardous.
5.
General Notes see Certification drawing for IS1 resp. IS1+
Remote I/O System No. 9400 6 031 004 1
WARNING:
Do not disconnect equipment when a flammable or combustable atmosphere is present.
AVERTISSEMENT:
Ne pas débrancher l’équipement en présence d’atmosphère inflammable ou combustible.