Parameterization and Commissioning
20
162278 / 9440609310
2020-10-22·BA00·III·en·08
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
CPU & power module
for Zone 2/Class I, Div. 2
Series 9440/15
Status information display for the I/O module
The following displays show the same design for all I/O modules.
LCD display
Display/function
12268E00
Display of the slot, module type and module status.
Possible module statuses:
Status information on the
LCD display
Meaning
Prio
IOM no response
Communication with the module is not
possible. The module is defective or not
connected, or both BusRails and/or the
BusRail connecting cable are damaged
1
Hardware failure
The module reports a hardware fault
2
conf unequal mod
Configuration error or the wrong
module was plugged in
3
HW disable outp.
Outputs disconnected by an external
switch (Plant-Stop)
(only with DOM 9475/2)
4
prim. Rail fail
No communication via primary
BusRail data bus
5
red. Rail fail
No communication via redundant
BusRail data bus
5
module OK/mode: x
Module is OK. No module error.
Signal errors are still possible.
The configured operating mode
(mode:x) is also displayed
6
In case of several faults, only the fault with the highest priority is displayed.
After eliminating this fault, the fault with the next highest priority is displayed.
12269E00
Display of the firmware and hardware revision.
12270E00
Display of the serial number.
slot 2: AOM
module OK/mode:0
slot
1:
AOM
FW 02-04, HW ‘E’
slot
3:
AOM
SNo: 123456-7890