CPU & power module
for Zone 2/Class I, Div. 2
Series 9440/15
Display of the CPM status information
Switch to a specific module display
LCD display
Display/function
12260E00
Status and fieldbus address of the device.
12264E00
Type of coupling
12265E00
Status of the device.
Possible status information:
Status information on the LCD display Meaning
No error
No error
Hardware fail (1)
Hardware error detected
Hardware fail (2)
Wrong hardware identification
Hardware fail (3)
No communication between CPR and
IOP
DataExch AS
Data Exchange with automation
system, configuration via Profibus
DataExch AS (2)
Data Exchange with automation system
No DataExch
No data exchange
Config/para fail
Configuration or parameter error
Quit DataExch
No more data exchange
12266E00
Press the
▲
and
▼
buttons simultaneously.
To switch back to module level of the device.
12267E00
Press the
▲
and
▼
buttons simultaneously.
To switch back to main display of the device.
LCD display
Settings
12258E00
• Initial display (shown on the left)
12259E00
• Press the
▲
and
▼
buttons to switch from the system level to the module
level. The following display appears (shown on the left).
• Select the desired module by pressing the
▲
or
▼
button.
• Press the
▲
and
▼
buttons simultaneously. The display switches to the
information level/service level.
CPM
active
FB addr :
5
CPM
information
Modbus
V10-00
CPM
status
config/para fail
CPM
active
back
CPM
active
exit menu
FBAdr
FB
I/O
120
OK
OK
CPM
active
9440/15-01-11