GRP Flameproof Visual Signal - 5 Joule
Series FL6S
5
Technical data
Explosion Protection
Global (IECEx)
Gas and dust
IECEx BAS 14.0064
IEC 60079-0: 2011 / IEC 60079-1: 2007 / IEC 60079-31: 2013
Ex d IIB T* Ta -** ... +** °C Gb
Ex d IIC T* Ta -** ... +** °C Gb
Ex tb IIIC T*** °C Ta -** ... +** °C Db IP66
Europe (ATEX)
Gas and dust
Baseefa14ATEX0126
EN 60079-0: 2012 / EN 60079-1: 2007 / EN 60079-31: 2009
(IEC 60079-31: 2013)
E
II 2 G Ex d IIB T* Ta -** ... Ta +** °C Gb
E
II 2 G Ex d IIC T* Ta -** ... Ta +** °C Gb
E
II 2 D Ex tb IIIC T*** °C Ta -** ... +** °C Db IP66
Product variant table
Certifications and certificates
Certificates
IECEx, ATEX, Kazakhstan (TR), Russia (TR), Belarus (TR)
Ambient conditions
Operating
temperature range
Power and
voltage
Temperature
class
Max. surface
temperature
Ambient temperature
range
5 J 24 V DC T6
T73 °C
-60 to +40 °C
T5
T88 °C
-60 to +55 °C
T4
T103 °C
-60 to +70 °C
5 J 48 V DC T6
T73 °C
-60 to +40 °C
T5
T88 °C
-60 to +55 °C
T4
T103 °C
-60 to +70 °C
5 J 115 V AC T5
T83 °C
-60 to +40 °C
T4
T113 °C
-60 to +55 °C
5 J 230 V AC T6
T75 °C
-60 to +40 °C
T5
T90 °C
-60 to +55 °C
T4
T105 °C
-60 to +70 °C
24/48 V DC -50 to +70 °C
115 V AC
-55 to +55 °C
230 V AC
-55 to +70 °C