Technical Data
6
149915 / 8562606300
2012-08-16·BA00·III·en·06
Residual current circuit-breaker with
integral overcurrent protection
8562/5
Rated switching capacities
*) only for type 8562/54-2465-160-4; 8562/54-2475-160-4; 8562/54-2480-160
**) with series circuit of 2 poles
Type
8562/5
8562/54-246.-...
8562/54-247.-...
8562/54-248.-...
Breaking capacity
6 resp. 10 kA 2 pole;
10 kA 1 pole + N (25 kA to IEC)
10 kA 2 pole;
25 kA 2 pole (only Type 8562/54-2480-160)
Version
Type A, pulse current sensitive to IEC/EN 61009
Characteristics
Short circuit protection
*) Only types: 8562/54-2465-160-4; 8562/54-2475-160-4; 8562/54-2480-160
Ambient temperature
- 20 ... + 60 °C In case of different temperature range please consider correction factor!
Poles Series with 6 kA
Series with 10 kA
Series with 25 kA
Vol-
tage
(V)
Cur-
rent
(kA)
Vol-
tage
(V)
Cur-
rent
(kA)
Vol-
tage
(V)
Cur-
rent
(kA)
AC acc. to
IEC/EN 60898
1 - 2
I
cn
/
I
cs
230 /
240
6
I
cn
230 /
240
10
I
cn
--
--
2*
--
--
--
I
cn
230
10
I
cn
230
25
AC acc. to
IEC/EN 60947-2
1
I
cu
240
10
I
cu
240
15
I
cu
--
--
1+N,
2
I
cu
127
30
I
cu
127
40
I
cu
--
--
240
20
240
30
--
--
2*
--
--
--
I
cu
230
25
I
cu
230
25
DC acc. to
IEC/EN 60947-2
(time constant 15 ms)
1
I
cu
/
I
cs
60
20
I
cu
/
I
cs
60
25
I
cu
/
I
cs
--
--
2
125
25
125
30
125
(5 ms)
15
(5 ms)
DC acc. to
IEC/EN 60898
(time constant
(
4 ms)
2
--
--
--
125**
10
125
(5 ms)
15
(5 ms)
Characteristic
to IEC/EN 60898
B
C
Rated current range
6 ... 40 A
6 ... 40 A
Loads
> Electric heatings
> Lighting
> Socket outlet circuits
> Control circuits
e.t.c.
> Operating equipment
> Light fitting groups
> Motors
> Transformers
e.t.c.
Normal temperature
30 °C
30 °C
Thermal overload trip
1.13 ... 1.45 I
n
1.13 ... 1.45 I
n
Magnetic trip
3 ... 5 I
n
5 ... 10I
n
Back-up protection with preceding fuse
Miniature circuit-breaker
Preceding fuse type gG
for tripping characteristic
C
B
B, C
Type
Rated current I
N
[A]
min. rated current
[A]
max. rated current
[A]
8562/5
1
4
--
--
2
8
--
63
3
10
--
6
20
10
80
10
25
16
16
40
20
16*
--
--
100*
20
50
32
100
25
63
40
Содержание 8562/54-246 Series
Страница 2: ......
Страница 3: ...Betriebsanleitung Fehlerstromschutz schalter mit Überstromauslöser 8562 5 ...
Страница 16: ...Operating Instructions Residual current circuit breaker with integral overcurrent protection 8562 5 ...
Страница 29: ......
Страница 30: ...149915 8562606300 2012 08 16 BA00 III de en 06 ...