Technical Data
4
149915 / 8562606300
2012-08-16·BA00·III·en·06
Residual current circuit-breaker with
integral overcurrent protection
8562/5
6
Technical Data
Type
8562/5
8562/54-246.-...
8562/54-247.-...
8562/54-248.-...
Explosion protection
Gas explosion protection
ATEX
E
II 2 G Ex d e IIC Gb
E
I M 2 Ex d e I Mb
E
II 2 G Ex d e IIC Gb
E
I M 2 Ex d e I Mb
IECEx
Ex d e IIC
Ex d e I
Ex d e IIC
Ex d e I
Certificates
ATEX
PTB 02 ATEX 1049 U
PTB 02 ATEX 1049 U
IECEx
IECEx PTB 06.0062U
IECEx PTB 06.0062U
Electrical data
Rated insulation voltage
500 V
500 V
No. of poles
1 pole + N; 2 pole
2 pole
Rated operational voltage
127 ... 230 V AC
133 ... 230 V AC
125 V DC with 2 contact strips connected in
series
Minimal voltage U
bmin
Maximal voltage U
bmax
250 V AC; 53 / 120 V DC
253 V AC
Rated working and
leakage currents
I
N
= 6 ... 40 A;
I
Δ
N
= 10 / 30 / 100 / 300 mA
I
N
= 6 ... 40 A;
I
Δ
N
= 10 / 30 / 100 / 300 mA
Tripping time at rated
residual current
1 x 1.4 I
Δ
N
(
300 ms
5 x 1.4 I
Δ
N
(
40 ms
1 x 1.4 I
Δ
N
(
300 ms
5 x 1.4 I
Δ
N
(
40 ms
Working area of the
control unit
180 ... 255 V
180 ... 255 V
Rated frequency
50 ... 60 Hz
50 ... 60 Hz
Impact strength
250 A, 8 / 20
m
s
250 A, 8 / 20
m
s
Service life
Mechanical
2x10
4
switching cycles
2x10
4
switching cycles
Electrical
10
4
switching cycles
10
4
switching cycles
Utilization category
A (acc. to IEC/EN 60947-2)
A (acc. to IEC/EN 60947-2)
Isolation function
yes (IEC/EN 60947-2)
yes (IEC/EN 60947-2; IEC/EN 60898-1;
EN/DIN 60664-1)
Pulse resistance
6 kV
(
6,2 kV
1-pole + N:
100 V AC
2-pole:
127 V AC
2-pole:
12 V AC; 12 V DC