Arrangement and Assembly
8
149915 / 8562606300
2012-08-16·BA00·III·en·06
Residual current circuit-breaker with
integral overcurrent protection
8562/5
7
Arrangement and Assembly
7.1 Mounting Orientation
Type
8562/5
8562/54-246.-...
8562/54-247.-...
8562/54-248.-...
Auxiliary contact
Version
see circuit diagrams
see circuit diagrams
Rated working voltage
max. 255 V AC
max. 255 V AC
Rated working current
5 A at 230 V AC
1 A at 60 V DC
2 A at 230 V AC
1 A at 400 V AC
2 A at 60 V DC
Coupling relais
Coil tension U
B
220 V
--
Minimum switching
current
10 mA
--
Minimum switching
current
5 A
--
Switching capacity
min. 250 mW
--
Please contact the manufacturer if operating conditions are non-standard.
Further technical data is given in the STAHL catalogue or is available upon request.
The temperature class depends upon where the protective enclosure is installed.
Change the Miniature Circuit-Breaker at the end of its service-life to guarantee ongoing
protection!
Upstream fuse/downstream Miniatur Circuit-Breaker for back-up protection
I
cc max
: 100 kA (80 kA, 400 V with fuse)
These circuit-breakers are explosion-protected devices to IEC/EN 60079-0.
They must be fitted into an enclosure with type of protection increased safety “e“, e.g.
enclosure Type 8146/5 from R. STAHL Schaltgeräte GmbH.
04934T00
Vertical,
Handle at the bottom
Содержание 8562/54-246 Series
Страница 2: ......
Страница 3: ...Betriebsanleitung Fehlerstromschutz schalter mit Überstromauslöser 8562 5 ...
Страница 16: ...Operating Instructions Residual current circuit breaker with integral overcurrent protection 8562 5 ...
Страница 29: ......