![Stahl 8485 Series Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/stahl/8485-series/8485-series_operating-instructions-manual_1357856068.webp)
Appendix A
32
204166 / 848560300010
2021-08-06·BA00·III·en·12
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Grounding monitoring device
Series 8485
Function
LED display
Grounding status
Reaction of grounding
monitoring device
20331E00
Clamp not connected,
device not used
Grounding defective
• Red indicator lamp
ON
• Green indicator
lamp OFF
• Relays R1 and R2
are de-energised
20332E00
Clamp is directly
connected to ground,
for example via the
loading platform
Grounding defective
• Red indicator lamp
ON
• Green indicator
lamp OFF
• Relays R1 and R2
are de-energised
20333E00
Clamp connected to
road tanker
Grounding OK
• Red indicator lamp
OFF
• Green indicator
lamp ON
• Relay R1 is
energised and
relay R2 is de-
energised
20334E00
Clamp connected to
road tanker Road
tanker is grounded
subsequently
(e.g. via the filling
arm)
Grounding OK
• Red indicator lamp
OFF
• Green indicator
lamp ON
• Relays R1 and R2
are energised
Relay R2 is energised if the resistance of the grounding loop of the tanker is
< 10 Ω.
Ambient conditions
Ambient temperature
-
55 to +60 °C
Storage temperature
-
55 to +60 °C
The device must always remain switched on at a temperature lower than -40 °C.
Mechanical data
Degree of protection IP65
Device version
Flameproof enclosure (Ex d)
Material
Enclosure
Aluminium
Weight
12.1 kg
Technical data
R1 R2
R1 R2
R1 R2