Operation, Installation and Maintenance Manual for 6414/11-Series
ID-No.:
240912 / 6414603300
Publication Code: 2015-04-30:BA00.lll.en.00 Page - 8 - of 17
Technical Data
Mounting / Installation
Cable Glands
1x M20/M25 left and 2x M20/M25 Right, 1x cable glands and 2 stopping plugs as standard.
(Others or on Special request - Certified single/double compression glands)
Connection
Spring clamp terminal
up to 4 mm
2
3-pole (2x L1, 2x N, 2x PE)
5-pole (2x L1, 2x L2, 2x L3, 2x N, 2x PE)
Screw terminal
up to 6 mm
2
3-pole (2x L1, 2x N, 2x PE)
5-pole (2x L1, 2x L2, 2x L3, 2x N, 2x PE)
Pendant light fitting
Light fitting top has 2No.’s of M8 threaded rivets which allow use of different mounting parts, e. g. ring bolts.
Wall-mounting light fitting
Each end is fitted with one M8 threaded bolt. The light fitting is hooked-in by these bolts to the wall mounting brackets and secured by
lock nuts.
Recessed light fitting
Two types of recessed fittings available:
1)
Flushing Frame to be fixed on to the Enclosure with the help of M6 Doom Head Bolt
2)
Flushing Frame Welded on to the Enclosure. (optional)
Note:
In both the above types, the mounting of the Luminaire is always done with the help of the ring bolts or the mounting
brackets.
Switch-off
Standard
Without Disconnect Switch
Optional
With
Disconnect Switch
Light technical data
Lamps
Two-pin fluorescent lamps; 26 mm diameter; for holder G13
2 x 18 W; 4 x 18 W; 2 x 36 W; 4 x 36 W; 2 x 58 W; 4 x 58 W
Installation notes
Looping through of cables
There are 2 cable entries on the connection side for looping through of connection cable (entry and exit on one side).
Through wiring
Standard
Luminaires Without Through Wiring
Optional:
Luminaires are equipped with internal through wiring Incoming and outgoing leads, can be connected on the opposite sides.
Terminals: see Technical data, Wiring cross-section: 2.5 mm2 for max. 12 A
6.
Transport and Storage
•
Transport and storage are only permitted in the original packaging.
•
Store the device in a dry place (no condensation) and vibration-free.
•
Do not drop the device.
7.
Mounting & Installation Notes
DANGER
Explosion hazard due to incorrect installation of the device!
Non-compliance results in severe or fatal injuries.
•
Carry out installation strictly according to the instructions and national safety and accident prevention regulations to maintain the explosion
protection.
•
Select and install the electrical device so that explosion protection is not affected due to external influences, i.e. pressure conditions,
chemical, mechanical, thermal and electric impact such as vibration, humidity and corrosion (see IEC/EN 60079-14).
•
The device must only be installed by trained qualified personnel who is familiar with the relevant standards.