Operation, Installation and Maintenance Manual for 6414/11-Series
ID-No.:
240912 / 6414603300
Publication Code: 2015-04-30:BA00.lll.en.00 Page - 7 - of 17
5.
Technical Data
Explosion Protection Certificats
ATEX, IEC Ex, PESO,
Zone Classification
Zone 2, 21 & 22
Explosion Protection Type
Equipment protection by type of protection "n", Equipment dust ignition protection by enclosure "t"
IECEx
IECEx BVS 14.0113
Ex nAc IIC T4
OR
Ex nA IIC T4 Gc
Ex tb IIIC T 80 °C
OR
Ex tb IIIC T 80°C Db
ATEX
BVS 14 ATEX E 164
II 3G Ex nA IIC T4
OR
II 3G Ex nA IIC T4 Gc
II 3D Ex tc IIIC T80°C
OR
II 3D Ex tc IIIC T 80 °C Dc
BVS 14 ATEX E 161
II 2D Ex tb IIIC T80°C
OR
II 2D Ex tb IIIC T 80 °C Db
Electrical Data
Ballast
6414/11..-....-....-..
Lamp Start
Cold start
Voltage
220 ... 240 V AC
DC voltage in case of ignition
198 … 264 V DC
DC voltage during operation
176 … 264 V DC
Frequency
0 / 50 … 60 Hz
Lamp operation DC
2-lamp
Lamp standard
IEC 60081
Lamp power
18, 36, 58 W
Nominal current
2x 18 W 150 mA
4x 18 W 300 mA
2x 36 W 300 mA
4x 36 W 600 mA
2x 58 W 480 mA
4x 58 W 960 mA
Lamp Wattage
18W, 36W & 58W Versions available with 2 lamps / 4 lamps options
Light guides
Reflector plate, can be swung out
Power factor cos
Cos
> 0.97
Ambient Operating Temp. (Ta)
Mechanical data
Degree of protection
IP 65
IP 64 with breathing gland 8162
IP 66 with Flushing Frame
acc. IEC 60598
Protection class
I (with internal PE connection)
Material
Enclosure
Standard:
Sheet-steel, powder-coated, colour white, similar to RAL 9016
Special:
Stainless steel 1.4301 (AISI 304) / 1.4404 (AISI 316L) – With Brushed finish
Mounting Bracket
Sheet steel Powder coated
Lens
Safety glass / Toughened Glass
Gasket
Silicone foam gasket in the luminaire housing
Luminaire Locking
Central locking can be opened/closed using a socket key M5 hex socket head driver
Scope
Ambient Temperature
Type 6414/11.6-....-
….-..
-30
°C ≤ T
amb
≤ +50 °C
Type 6414/11.4-....-
….-..
-30
°C ≤ T
amb
≤ +55 °C
Type 6414/11.2-....-
….-..
-30
°C ≤ T
amb
≤ +50 °C