The following tests and measures must be carried out during regular maintenance.
Check
Measures
the permissible ambient temperature
If exceeding the permissible ambient temperature or falling below the
device must be taken out of operation.
the enclosure components for formation
of cracks and damage.
Replace the exchangeable enclosure components. If the enclosure
components are non-exchangeable, the device must be taken out of
operation.
its intended use
If the device is not used according to its intended use, it must be taken
out of operation.
the cables for ageing and damage
replace damaged or aged cables.
the seals for ageing and damage
replace damaged, aged and porous seals and completely change
enclosure components with foamed seal.
if the conductors are clamped properly
clamp loose conductors tightly.
10.1.1 Replacement of lamps
Only use fluorescent lamps with pins made of brass.
•
Insert both the lamp bases into the holder guide slots until the stop is reached.
•
Move lamp to its operating position by turning it to the right or the left.
•
Dismounting is carried out in reverse order.
Important notes:
•
The lamp bases and pins must be undamaged.
•
The holders have a spring-loaded length adjustment facility of 2.5 mm each.
•
Make sure that the lamp has been fitted properly. When it has been turned, the
lamp is locked in position.
•
Replace the lamps in due time.
•
Observe the service life specified by the manufacturer.
•
EOL- safety shutdown: The EB switches off the lamp at the end of the service
life.
10.1.2 Cleaning
NOTE
The luminaire is marked with the warning "Clean with damp cloth only".
Clean the device only with a damp cloth.
Use water or mild cleaning agents.
Do not use abrasive, scratching and aggressive detergents or solvents.