Binary output
Series 9175
8
Operation
8.1
Operation
The binary output device is intended for the intrinsically safe operation of solenoid valves,
LED indicator lamps, etc. When controlling solenoid valves, always note the characteristic
values of the valve. Active line fault detection can, under certain circumstances, prevent the
solenoid valve from falling.
8.2
Displays
The LEDs on the device indicate the operating state of the device
(see also the "Device design" chapter).
8.3
Troubleshooting
If the error cannot be eliminated using the specified procedures:
▶
Contact R. STAHL Schaltgeräte GmbH.
For rapid processing, have the following information ready:
• Type and serial number of the device
• Purchase information
• Error description
• Intended purpose (especially input/output circuit)
LED
Colour "ON" LED
"OFF" LED
"PWR" LED green Device is supplied with auxiliary
power
Device is not in operation,
power supply not available
"LF1" LED
red
Line fault detection for channel 1
activated
Line fault detection for channel 1
not activated
"LF2" LED
red
Line fault detection for channel 2
activated
Line fault detection for channel 2
not activated
"OUT1" LED yellow Output channel 1 activated
Output channel 1 not activated
"OUT2" LED yellow Output channel 2 activated
Output channel 2 not activated
Error
Cause of error
Troubleshooting
"PWR" LED is off
Auxiliary power failure or defective
miniature fuse
• Check the auxiliary power
supply and restore if
necessary.
• If the fuse is defective,
have the device repaired.