11
5. Bypass Voltage Windows
:
Sensitivity: Select Sensitivity Low/Sensitivity
High**
Sensitivity Low
Sensitivity High
120V System
90V
~
130V
97V
~
130V
230V System
180V
~
260V
194V
~
260V
6. Syn-Frequency Window
:
Select 3Hz/1Hz Inverter Freq synchronizing
range
7. Com Port
:
Select the Com Port of PC
8. Click on
“Write” to confirm the configuration settings. The UPS will beep
twice to acknowledge setting is successful.
9. Turn off the UPS and unplug input power cord from AC Power Utility
receptacle to shutdown whole unit without internal power supply existing,
after setting is complete. 3 seconds later reconnect input power cord into
AC Power Utility receptacle and turn on the UPS, referring to the section
4.4 Operation. The UPS will perform in new settings.
Note:
*CF50/CF60 = Frequency Converter mode 50 to 60Hz or 60 to 50Hz. When
operating in CVCF mode the full load rating of the UPS is reduced to 75%
(1000va becomes 750va). Additionally, the AC low transfer point based
on load percentage is referred to the new power rating.
160Vac load rating is 66% ~ 100% (495va ~ 750va)
140Vac load rating is 33% ~ 66%
120Vac load rating is 0% ~ 33%
**Sensitivity Low
:
90/180~130/260V, High: 97/194~130/260V
Содержание UniStar C
Страница 1: ...Form No 003 2308 Rev C 1K 2K 3K UniStar C Intelligent True On Line UPS User Manual ...
Страница 9: ...8 3 2 Rear Panel Descriptions 120V 1KVA 10 8 7 1 2 3 5 4 6 2KVA 3KVA ...
Страница 19: ...18 4 3 Set up Tower Configuration Setup Step 1 Power Module Battery Module Step 1 ...
Страница 20: ...19 Rack Mount Configuration Setup Step 1 Step 2 Step 3 ...
Страница 21: ...20 Step 4 Step 5 ...
Страница 27: ...26 Q1 Q2 R1 R2 S ...
Страница 28: ...27 T U1 U2 U3 V ...
Страница 32: ...31 4 4 3 Battery Replacement Step 1 Step 2 ...
Страница 33: ...32 Step 3 Step 4 1KVA 2K 3KVA ...