Dry Contact card SC-Relay (Optional)
8.1 The pin assignments of 10-Pin Terminal
:
1
UPS on Bypass mode (Bypass)
2
Utility Normal (Normal close contact)
3
Utility Normal (Normal open contact)
4
Inverter On
5
Battery Low
6
Battery Bad or abnormal
7
UPS Alarm
8
Common
9
Shutdown UPS po) signal
10
Shutdown UPS negative(-) signal
The shutdown function will be activeated, after a +6~+25Vdc is put
between pin 9 and pin 10 for 5 seconds.
The capacity of each relay contact is 40Vdc/25mA.
Installation Position
:
Optional Slot.
Flexible signal output for N.C.(Normal Close) or N.O.(Normal Open)
contact by shorting pin1-2 or pin2-3 form JP1-5.
The shutdown function will be enabled 1 minute after a blackout occurs if
pins 1-2 of both CN1 and CN6 are shorted. Or, the shutdown function
can only be enabled by pin9-10 of CN3 if the pin2-3 of both CN1 and
CN6 are shorted.