User Manual
CANopen/PROFIBUS DP Gateway
GT200-DP-CO
WWW.SSTCOMM.COM
35
Number of bytes: Number of bytes of mapping item
Mapping address: Memory address mapped in the gateway (Read only)
COB-ID: The CAN ID (decimal) of CANopen PDO:
Default value of Transmit PDO command: 384(0x180) + node ID or 640(0x280) + node ID or 896 (0x380) +
node ID or 1152(0x480) + node ID
Default value of Receive PDO: 512(0x200) + node ID or 768(0x300) + node ID or 1024 (0x400) + node ID
or 1280 (0x500) + node ID
Mnemonic description: Users can input the description of project configuration items here; these are not
downloaded to gateway actually
5.1.4.5 Comment Interface
Comment interface displays the explanation of relevant configuration item. When the configuration item is
"COB-ID", the comment interface is shown as below:
5.1.5 Hardware Configuration
Communication menu is shown as below:
5.1.5.1 COM Configuration
The software can scan usable serial port automatically, and show it in the port list. Finish all configurations,
click "OK" and save settings.
Remark
: When you finish setting port, and other parameters are fixed value: 57600, 8, ODD, 8, 1.