Errol Control: Function selection item. Non-zero means to use life guard protocol. Zero means to use
heartbeat protocol. The default is 0. The range is 0~2000.
The Cycle for RPDO Transmission: The Cycle for RPDO Transmission is based on 1ms. Zero means to use
the mode of change of value output; Non-zero means to send all RPDO according to the cycle. Sending cycle
equals setting value, the default value is 0. The range: 0~60000.
Output Data Processing: When PROFIBUS DP is off, the RPDO data of DP output buffer will Clear and
Hold; “Clear” means to set the data to zero; “Hold” means to keep the data unchanged before DP is off.
The Cycle for SDO Transmission: The Cycle for SDO Transmission, is based on 1ms. Zero means Download
SDO uses mode of change of value output, Upload SDO uses the mode of non-stop reading slave data; Non-
zero means to send all SDO according to the cycle. Sending cycle equals setting value, the default value is 0.
The range: 0~60000.
SDO Send Concurrently: Disable: The SDO request for a node must wait for the node’s response before
initiating the next SDO request; Enable: Sending SDOs command requests of different nodes concurrently.
Retries of SDO: The CANopen master sends an SDO request command but does not receive a response from
the slave, and the master repeatedly sends this SDO request command. Range: 0~5, default: 0
SDO Poll Delay Time: The CANopen master sends the SDO request command and receives the response
from the slave. The master needs to delay for a while before sending the next SDO request command. This
period of time is the SDO command polling delay time. Unit: ms, Range: 0~60000ms, default: 0ms.
5.1.4.3 Node Configuration
In the device interface, left click on a node and then the configuration interface is shown as below: