3.4.2 LED Display
In the configuration mode, LED display CF;
In the debug mode, LED displays “db”;
In the run mode, LED displays PROFIBUS DP slave address.
3.4.3 PROFIBUS DP Address Setting Button
The configuration button on the panel can set the PROFIBUS DP slave address.
In run mode of GT200-DP-CO, LED display is always on and displaying the current PROFIBUS DP address.
Quickly press (double-click) the button twice in succession, the high bit starts to flash, and the low bit is always
on, click the button to add 1 to start setting the high bit of PROFIBUS DP address. Long-press the button for 3
seconds, the high bit is always on, and the low bit starts to flash. Click the button to add 1 to start setting the low
bit of PROFIBUS DP address. At last, long-press the button again for 3 seconds, the address flashing three times
shows that the address is set successfully. If no button action within ten seconds, the gateway exits the status of
setting address and continues to display the original address. The configurable range of PROFIBUS DP address is
0 to 99 (Decimal).
PROFIBUS DP address setting method is as follow: