User Manual
CANopen/PROFIBUS DP Gateway
GT200-DP-CO
WWW.SSTCOMM.COM
10
3.1 Indicators
Indicators
Status
Description
PROFIBUS
Status
PBF
(red)
On
PROFIBUS DP connection has not been established
Off
PROFIBUS DP connection has been established
STA
(green)
Blinking
Exchanging data
Off
PROFIBUS DP status is abnormal
CANopen
Status
ERR
(bicolor)
Green on
The CAN network is normal
Red on
Bus Off
Red, Green and Off
alter alternately
The error counter of CAN controller reach or exceed alarm
value
RUN
(bicolor)
Green on
Node is in the run state
Green light on every
200ms, off every
1000ms
Node is in the stop state
Green light on every
200ms, off every
200ms
Node is in the pre-run state
Serial Port
TX
Red blinking
Serial port is sending data
Red off
Connection not established or goes wrong
RX
Green blinking
Receiving data
Green off
Connection not established or goes wrong
3.2 DIP Switch
Run mode to Configuration mode: Set bit2 to ON, the gateway enter into Configuration mode and no need to
restart the gateway (power off and power on).
Off
On 1 2