SOLID STATE INSTRUMENTS
INSTRUCTION SHEET
PRR-16 PULSE RECEIVER BASE UNIT
Revision: 4/3/22
OUTPUT CONFIGURATION -
The PRR-16 contains four solid state Form A dry-contact outputs, two each for
both "K", "Y" and "Z" outputs. Each solid state output is limited to 100mA@ 250VAC, 800mW maximum. Fuses
are sized at 1/10th amp (100mA). Do not exceed this rating as the device will be destroyed. Transient voltage
protection for the contacts of the solid state relays are provided by MOVs on board.
a division of Brayden Automation Corp.
6230 Aviation Circle, Loveland, Colorado 80538
Phone: (970)461-9600
E-mail:[email protected]
RSSI SIGNAL STRENGTH INDICATOR -
The PRR-16 contains a 3-LED bar graph that tells the relative signal
strength coming from the Transmitter. It consists of three RED LEDs in the upper left-hand corner of the board.
14
GND
K
Y
Z
NEU
120V
OUTPUT #1
POWER SUPPLY
INPUT
STATUS LEDS -
The PRR-16 has four status LEDs to indicate the status of the system at all times. See Page
__ for description of the Status LED functions.
POWER INPUT -
For a power supply of 120 VAC, use the the
L1
terminal for the "hot" lead. For 208 to 277
volts AC, use the
L2
terminal for the "hot" lead. Connect the Neutral lead to the
NEU
terminal. Connect the
GND
terminal to Ground. GROUND MUST BE CONNECTED TO A GOOD ELECTRICAL SYSTEM GROUND!!!
SIGNAL INPUT -
The PRNR-1600 receiver/antenna unit connects to the 9-position connector labelled TB2.
Terminals are numbered in the same order on the PRNR-1600 and the PRR-16. Connect #24AWG 8-conductor
(4-twisted pairs) shielded control cable between the PRNR-1600 receiver/antenna board and the PRR-16
making sure that all connections are matched up on both ends: 1 to 1; 2 to 2; etc. Make sure that the control
cable's shield is connected to position 9 on each end.
277V
From PRNR-1600
Receiver/Antenna Unit
L2
L1
N
G
Z2
Y2
K2
1
2
3
4
5
6
7
8
9
K
Y
Z
Z1
Y2
K1
OUTPUT #2
GENERAL -
The PRR-16 serves as a base unit, and termination
point for the PRNR-1600 receiver radio/antenna unit. It contains
a power supply, output relays and all connection points for the
receiver/antenna unit.
SCK-
SDI+
SDI-
SCK+
+V
GND
BR/W
BRN
OR/W
GR/W
GRN
SHLD
SDO+
SDO-
ORG
BL/W
BLU
SLVR
TB2
TB1
24AWG (min)/8-conductor (4-twisted
pair) with shield 100' max.
ENCLOSURE -
The PRR-16 base unit is mounted on a aluminum base and is designed to be mounted into
another electrical enclosure suitable for the application. Optional NEMA 3R and 4X raintight enclosures are
available.
Lo
w
(
F
a
ir
)
Med (Good)
High (Ex
c
e
ll
e
n
t)
PRR-16
Receiver
Base Unit
(Not to Scale)
1
2
3
4
RSSI
Learn S
ta
tu
s
D
IP
T
ra
n
sfer
Data Transfe
r
Heartbea
t
STATUS LEDs