background image

7

7.  Auto-Restart

a.  Use the ‘Up’ and ‘Down’ arrow buttons to enable/

disable auto-restart.  Press ‘Enter’ to accept the new 

selection.

b.  Press ‘ESC’ to return to the Main Menu. 

E.   Dryer Startup
NOTICE: Energize Dryer for 24 hours prior to starting 

refrigeration compressor!  Failure to follow these notices may 

result in a non-warrantable compressor failure.
1.   Start dryer 15 minutes prior to compressed air flow.
2.  On water-cooled models: begin cooling water flow prior 

to compressor startup.

3.  Check for proper electrical voltage.
4.  Slowly pressurize unit air side by opening inlet isolation 

valve. Check for leaks.

5.  After 15 minutes, open outlet isolation valve slowly.
6.  Close air bypass valve.
7.  Select dryer operating mode with Manual/Schedule 

mode button.

NOTE: Check for correct phasing of unit. 
On air-cooled models: check fan rotation (air must be pulled 

through the condenser).  Fans may not start immediately or 

may cycle on and off.  If rotation is in the wrong direction 

follow the procedure below. 
On water-cooled models: After starting dryer if an unusual 

noise is heard and the discharge line does not get hot, 

stop the dryer, reverse two power leads, restart, and verify 

discharge line gets hot.

F.   Dryer Operation
1.  Manual Mode - Pushing the On/Off button will cause the 

dryer to turn on or turn off.  Dryer status is indicated on 

the text display.  The compressor will begin cycling based 

on the glycol temperature.  The compressor LED will 

reflect the state of the compressor.

2.  Scheduled Mode - Pressing the Schedule Mode button 

will cause the dryer to toggle between scheduled and 

manual modes.  In scheduled mode the dryer will turn 

on/off based on the schedule entered during the dryer 

setup.  The compressor will cycle based on the glycol 

temperature when the dryer is on.

3.  Remote Mode - By closing the remote mode contact the 

dryer will enter a remote control mode.  The state of the 

dryer will be based on the remote control contact.  If the 

contact is closed the dryer will run, if the contact is open 

the dryer will remain off.

NOTE:  The dryer may be returned to manual mode at any 

time by pressing the schedule button. Manual Mode will 

appear on text display. To re-enable scheduled operation, 

press the schedule button again.

Auto-Restart

Disabled (Factory Default) - Following a power interruption 

the dryer will begin operation in manual mode with the dryer 

off.
Enabled - Following a power interruption the dryer will return 

to the previous operating mode and will turn the dryer on or 

off based on the mode.

Manual Mode - Dryer will return to state it was in prior to 

power failure.
Scheduled Mode - Dryer will be on or off based on the 

programmed schedule.
Remote Mode - Dryer will be on or off based on remote 

control contact

.

G.   Dryer Display
1.   Operating Mode - Displays the current date/time and 

operating mode.

2.   Drying Status - Displays the status of the dryer (on/off)
3.  Hours to Service - Displays the hours remaining before 

dryer service is required.

4.  Total Hours - Displays the total hours the dryer has been 

operating.

5.  Daily Run Time - Displays the average dryer load over the 

last 24 hours.

6.  Average Run Time - Displays the average dryer load over 

the last 30 days.

7.  Energy Savings - Displays the estimated annual energy 

savings based on the average dryer load over the last 30 

days.

8.  Glycol Temperature - Displays the glycol temperature 

reading. 

H.   Dryer Alarms

SERVICE DRYER - Indicates that the service interval 

for the dryer has expired.  Perform required dryer 

maintenance and reset using the alarm reset button. 
HIGH DISCHARGE PRESSURE - Indicates that the 

refrigeration compressor control circuit has opened 

because of high head pressure. The high pressure 

switch must be reset manually. After fixing the fault and 

resetting the pressure switch the alarm can be cleared 

using the alarm reset button. 
COMPRESSOR – Indicates that the compressor contactor 

has not engaged. Check the compressor contactor. 

Once the fault has been corrected the alarm can be 

manually cleared using the alarm reset button.
TEMPERATURE SENSOR FAILURE – Indicates a problem 

with the 10kOhm NTC Thermistor. Check to make sure 

the thermistor is properly connected to the control 

board and the resistance across the Thermistor is correct. 

Once the fault has been corrected, the alarm can be 

manually cleared using the alarm reset button.
HIGH TEMPERATURE - HIGH GLYCOL TEMPERATURE – 

Indicates that the dryer is overloaded or there is a 

problem with the refrigeration system leading to poor 

dryer performance. Once the fault has been corrected 

the alarm can be manually cleared using the alarm reset 

button.
HEATER – Indicates a problem with the crank case heater. 

The crank case heater should energize any time the 

dryer is off. Check to make sure the crank case heater is 

energized. Once the fault has been corrected the alarm 

can be manually cleared using the alarm reset button.
DRAIN – Indicates a problem with the electronic demand 

drain. Refer to the electronic demand drain manual for 

further information on how to correct the drain fault. 

Once the fault has been corrected the alarm can be 

manually cleared using the alarm reset button. 

Содержание HANKISON HES Series

Страница 1: ...OPERATION 5 3 0 MAINTENANCE 9 SIZING 9 ENGINEERING DATA Models 90 240 10 Models 280 675 11 Wiring Diagrams standard controller Models 90 140 115 1 60 12 Models 90 140 230 1 60 13 Models 190 540 14 15...

Страница 2: ...It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a not...

Страница 3: ...ed 40 to 110 F 4 to 43 C Water cooled 40 to 130 F 4 to 54 C E The installation of a flexible connection prior to the dryer is recommended to prevent possible damage from vibration NOTE Outdoor install...

Страница 4: ...cally discharges condensate NOTE It may be desirable to pipe the condensate from the Automatic Drain outlet to a suitable drain B Models 90 140 Separator has a knurled fitting with flexible drain tubi...

Страница 5: ...ll illuminate Compressor will run until glycol mixture is cooled The refrigeration unit will then turn off and the compressor on light will be extinguished SLOWLY pressurize the dryer with compressed...

Страница 6: ...10 dryer alarms sorted in chronological order b Press ESC to return to the Main Menu NOTE Hold the alarm reset button to clear the alarm history 5 Energy Cost a Use the Up and Down arrow buttons to s...

Страница 7: ...and will turn the dryer on or off based on the mode Manual Mode Dryer will return to state it was in prior to power failure Scheduled Mode Dryer will be on or off based on the programmed schedule Remo...

Страница 8: ...ke up to two seconds as certain processing functions may require completion before serial port is acknowledged Dryer responds with line feed 0AH carriage return 0DH and character string 1 2 3 4 5 6 7...

Страница 9: ...C 54 C 30 50 80 100 125 150 175 200 250 2 0 3 4 5 5 6 9 8 6 10 4 12 1 13 8 17 2 1 24 1 40 1 55 1 61 1 67 1 71 1 75 1 77 1 81 0 92 1 07 1 19 1 25 1 30 1 34 1 37 1 39 1 43 0 71 0 83 0 95 1 00 1 05 1 08...

Страница 10: ...tage Range 104 127 187 253 Input Power Rated Flow watts 978 1 282 1 293 1 363 1 942 Minimum Circuit Ampacity 13 6 18 3 18 3 10 5 15 9 Maximum Overcurrent Protector amps 20 25 25 15 20 Compressor Rated...

Страница 11: ...1 2 5 3 0 3 6 50 Hz 1 6 2 0 2 3 2 8 3 3 Electrical Data Nominal Voltage 208 230 3 60 Voltage Range 187 253 Input Power Rated Flow watts 1 950 2 065 2 496 3 081 4 350 Minimum Circuit Ampacity 15 9 15 9...

Страница 12: ...G BAR G GND TCB 1 TCB 1 T2 T2 COMPRESSOR ON PILOT LIGHT 1 2 3 4 TEMPERATURE CONTROL BOARD 120 VAC 100 RTD G BAR G BAR PUMP T2 PUMP HARNESS FAN 1 HARNESS T2 FAN 1 FPS 1 T1 TCB 1 3 1 3 OVERLOAD C S R M...

Страница 13: ...T2 T2 POWER ON PILOT LIGHT G 1 2 3 4 TEMPERATURE CONTROL BOARD TCB 1 GND T2 TCB 1 G 230 VAC T1 T1 T1 PUMP T2 PUMP HARNESS T2 FAN 1 HARNESS FAN 1 FPS 1 T1 CR4 OVERLOAD 3 1 3 C S R MTR1 COMPRESSOR CAPAC...

Страница 14: ...T2 TB2 PE T3 T2 TB2 PE HEATER HARNESS H1 H2 HEATER 1 FPS 2 MTR4 FAN 2 FAN 2 HARNESS MTR2 FPS 1 FAN 1 FAN 1 HARNESS MTR1 COMPRESSOR COMPRESSOR HARNESS 43 42 35 36 37 38 39 40 41 34 31 32 33 30 29 28 2...

Страница 15: ...ER ENERGIZED X3 G N N TB2 G G TB2 X3 TEMPERATURE CONTROL BOARD 04 05 06 07 08 X3 2080 X3 2080 POWER ON PILOT LIGHT TB2 PE N N N 09 10 11 12 13 14 15 4 3 2 GND 1 120 VAC 2070 3 100 RTD HPS HPS SENSOR H...

Страница 16: ...16 WIRING DIAGRAM Standard Controller Model 675 Sheet 1 of 2...

Страница 17: ...17 WIRING DIAGRAM Standard Controller Model 675 Sheet 2 of 2 RTD...

Страница 18: ...18 WIRING DIAGRAM Advanced controller Models 190 540 460 VAC Sheet 1 of 2...

Страница 19: ...19 WIRING DIAGRAM Advanced controller Models 190 540 460 VAC Sheet 2 of 2...

Страница 20: ...20 WIRING DIAGRAM Advanced controller Model 675 460 VAC Sheet 1 of 2...

Страница 21: ...21 WIRING DIAGRAM Advanced controller Model 675 460 VAC Sheet 2 of 2...

Страница 22: ...22 WIRING DIAGRAM Models 190 675 575 460 3 60 Transformer Pack...

Страница 23: ...15 766 E 17 62 448 17 62 448 17 62 448 30 15 766 30 15 766 30 15 766 30 15 766 39 62 1006 39 62 1006 39 62 1006 F 19 62 498 19 62 498 19 62 498 32 15 817 32 15 817 32 15 817 32 15 817 41 62 1057 41 62...

Страница 24: ...pressure drop across dryer 1 Excessive air flow 2 Freezing of moisture in evaporator because of refrigeration system fault 3 Separator filter element clogged Check flow rate See D below Replace filte...

Страница 25: ...ervice interval specified has elapsed a Lack of condenser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch...

Страница 26: ...r Strainer Screen 3230672 3230672 3230672 3230672 3230672 3230672 3230672 3230672 3230672 3230672 High Refrigerant Pressure Switch 3230764 3230764 3230764 3230764 3230764 3230764 3230764 3230764 32307...

Страница 27: ...27 NOTES...

Страница 28: ...ERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER...

Отзывы: