SPX HANKISON HES Series Скачать руководство пользователя страница 6

6

D.  Advanced Controller (EMM) Setup

Press and hold Program Mode button until Main Menu 

appears.  Use the Up and Down arrow buttons to scroll 

through the menu choices.  Press Enter button in order 

to display the selected menu item.  Press ESC to exit the 

Main Menu and return to Display mode.

1.  Language selection

a.  Use the ‘Up’ and ‘Down’ arrow buttons to scroll 

through available languages.

b.  Press ‘Enter’ button to apply the current language 

selection.

c.  Push ‘ESC’ button to return to the Main Menu. 

2.  Setting Date & Time

a.  Use the ‘Up’ and ‘Down’ arrow buttons to change 

the selected field.  Press ‘Enter’ button to accept 

new value and move to the next field.

b.  Push ‘ESC’ to return to the Main Menu.
NOTE:  The selected value is indicated by a ‘_’.

3.  Setting Schedule

a.  Use the ‘Up’ and ‘Down’ arrow buttons to select the 

day of week and operation.  Press ‘Enter’ to accept 

new value and move to the next field.

b.  Use the ‘Up’ and ‘Down’ arrow buttons to select 

hours.  Press ‘Enter’ to accept the hours and move 

to the next field.

 

NOTE:  ‘IGNORE’ allows you to skip performing the 

specified action.

c.  Use the Up and Down arrow buttons to select 

minutes.  Press ‘Enter’ to accept the minutes and 

return to “Day of week/operation” selection. 

d.  Push ‘ESC’ when the schedule setup is complete to 

return to the Main Menu.

4.  Alarm History

a.  Use the ‘Up’ and ‘Down’ arrow buttons to 

scroll through the last 10 dryer alarms sorted in 

chronological order.

b.  Press ‘ESC’ to return to the Main Menu.
 

NOTE: Hold the alarm reset button to clear the alarm 

history.. 

5.  Energy Cost

a.  Use the ‘Up’ and ‘Down’ arrow buttons to select the 

desired currency.  Press ‘Enter’ to accept the new 

value and move to the next field.

b.  Use the ‘Up’ and ‘Down’ arrow buttons to select the 

energy cost.  Press ‘Enter’ to accept the new value 

and move to the previous field.

c.  Press ‘ESC’ to return to the Main Menu.

6.  Service Interval

a.  Use the ‘Up’ and ‘Down’ arrow buttons to program 

the desired service interval.  Press ‘Enter’ to accept 

the new service interval value.

b.  Press ‘ESC’ to return to the Main Menu. 

1.  Glycol Temperature Indicator
2.  Text Display
3.  Power LED
4.  Compressor LED
5.  Alarm / Service LED
6.  Schedule / Enter Button

a.  In Display Mode: Toggle between manual and 

scheduled dryer operating modes.

b.  In Setup Mode:  Enter a sub-menu or confirm a 

value.

7.  Setup Mode / Escape Button

a.  In Display Mode: Hold to enter setup mode.

b.  In Setup Mode: Press to exit current menu.

8.  Up Arrow

a.  In Display Mode: Move to previous display 

screen.

b.  In Program Mode:  Increment current menu/

value selection.

9.  Down Arrow

a.  In Display Mode: Move to next display screen

b.  In Program Mode:  Decrement current menu/

value selection.

10.  On/Off Button: Press to toggle the dryer on/off 

forces dryer to enter manual mode.

11.  Drain test: Press to momentarily open the 

electronic demand drains.

12.  Reset: Press to clear the current alarm message and 

alarm/service LED.

CONTROL PANEL

1

2

3

4

5

6

7

8

9

10

11

12

energy 

saving

AIR TREATMENT

Содержание HANKISON HES Series

Страница 1: ...OPERATION 5 3 0 MAINTENANCE 9 SIZING 9 ENGINEERING DATA Models 90 240 10 Models 280 675 11 Wiring Diagrams standard controller Models 90 140 115 1 60 12 Models 90 140 230 1 60 13 Models 190 540 14 15...

Страница 2: ...It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a not...

Страница 3: ...ed 40 to 110 F 4 to 43 C Water cooled 40 to 130 F 4 to 54 C E The installation of a flexible connection prior to the dryer is recommended to prevent possible damage from vibration NOTE Outdoor install...

Страница 4: ...cally discharges condensate NOTE It may be desirable to pipe the condensate from the Automatic Drain outlet to a suitable drain B Models 90 140 Separator has a knurled fitting with flexible drain tubi...

Страница 5: ...ll illuminate Compressor will run until glycol mixture is cooled The refrigeration unit will then turn off and the compressor on light will be extinguished SLOWLY pressurize the dryer with compressed...

Страница 6: ...10 dryer alarms sorted in chronological order b Press ESC to return to the Main Menu NOTE Hold the alarm reset button to clear the alarm history 5 Energy Cost a Use the Up and Down arrow buttons to s...

Страница 7: ...and will turn the dryer on or off based on the mode Manual Mode Dryer will return to state it was in prior to power failure Scheduled Mode Dryer will be on or off based on the programmed schedule Remo...

Страница 8: ...ke up to two seconds as certain processing functions may require completion before serial port is acknowledged Dryer responds with line feed 0AH carriage return 0DH and character string 1 2 3 4 5 6 7...

Страница 9: ...C 54 C 30 50 80 100 125 150 175 200 250 2 0 3 4 5 5 6 9 8 6 10 4 12 1 13 8 17 2 1 24 1 40 1 55 1 61 1 67 1 71 1 75 1 77 1 81 0 92 1 07 1 19 1 25 1 30 1 34 1 37 1 39 1 43 0 71 0 83 0 95 1 00 1 05 1 08...

Страница 10: ...tage Range 104 127 187 253 Input Power Rated Flow watts 978 1 282 1 293 1 363 1 942 Minimum Circuit Ampacity 13 6 18 3 18 3 10 5 15 9 Maximum Overcurrent Protector amps 20 25 25 15 20 Compressor Rated...

Страница 11: ...1 2 5 3 0 3 6 50 Hz 1 6 2 0 2 3 2 8 3 3 Electrical Data Nominal Voltage 208 230 3 60 Voltage Range 187 253 Input Power Rated Flow watts 1 950 2 065 2 496 3 081 4 350 Minimum Circuit Ampacity 15 9 15 9...

Страница 12: ...G BAR G GND TCB 1 TCB 1 T2 T2 COMPRESSOR ON PILOT LIGHT 1 2 3 4 TEMPERATURE CONTROL BOARD 120 VAC 100 RTD G BAR G BAR PUMP T2 PUMP HARNESS FAN 1 HARNESS T2 FAN 1 FPS 1 T1 TCB 1 3 1 3 OVERLOAD C S R M...

Страница 13: ...T2 T2 POWER ON PILOT LIGHT G 1 2 3 4 TEMPERATURE CONTROL BOARD TCB 1 GND T2 TCB 1 G 230 VAC T1 T1 T1 PUMP T2 PUMP HARNESS T2 FAN 1 HARNESS FAN 1 FPS 1 T1 CR4 OVERLOAD 3 1 3 C S R MTR1 COMPRESSOR CAPAC...

Страница 14: ...T2 TB2 PE T3 T2 TB2 PE HEATER HARNESS H1 H2 HEATER 1 FPS 2 MTR4 FAN 2 FAN 2 HARNESS MTR2 FPS 1 FAN 1 FAN 1 HARNESS MTR1 COMPRESSOR COMPRESSOR HARNESS 43 42 35 36 37 38 39 40 41 34 31 32 33 30 29 28 2...

Страница 15: ...ER ENERGIZED X3 G N N TB2 G G TB2 X3 TEMPERATURE CONTROL BOARD 04 05 06 07 08 X3 2080 X3 2080 POWER ON PILOT LIGHT TB2 PE N N N 09 10 11 12 13 14 15 4 3 2 GND 1 120 VAC 2070 3 100 RTD HPS HPS SENSOR H...

Страница 16: ...16 WIRING DIAGRAM Standard Controller Model 675 Sheet 1 of 2...

Страница 17: ...17 WIRING DIAGRAM Standard Controller Model 675 Sheet 2 of 2 RTD...

Страница 18: ...18 WIRING DIAGRAM Advanced controller Models 190 540 460 VAC Sheet 1 of 2...

Страница 19: ...19 WIRING DIAGRAM Advanced controller Models 190 540 460 VAC Sheet 2 of 2...

Страница 20: ...20 WIRING DIAGRAM Advanced controller Model 675 460 VAC Sheet 1 of 2...

Страница 21: ...21 WIRING DIAGRAM Advanced controller Model 675 460 VAC Sheet 2 of 2...

Страница 22: ...22 WIRING DIAGRAM Models 190 675 575 460 3 60 Transformer Pack...

Страница 23: ...15 766 E 17 62 448 17 62 448 17 62 448 30 15 766 30 15 766 30 15 766 30 15 766 39 62 1006 39 62 1006 39 62 1006 F 19 62 498 19 62 498 19 62 498 32 15 817 32 15 817 32 15 817 32 15 817 41 62 1057 41 62...

Страница 24: ...pressure drop across dryer 1 Excessive air flow 2 Freezing of moisture in evaporator because of refrigeration system fault 3 Separator filter element clogged Check flow rate See D below Replace filte...

Страница 25: ...ervice interval specified has elapsed a Lack of condenser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch...

Страница 26: ...r Strainer Screen 3230672 3230672 3230672 3230672 3230672 3230672 3230672 3230672 3230672 3230672 High Refrigerant Pressure Switch 3230764 3230764 3230764 3230764 3230764 3230764 3230764 3230764 32307...

Страница 27: ...27 NOTES...

Страница 28: ...ERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER...

Отзывы: