IM-P707-01
CTLS Issue 1
73
SP8-10 Smart positioner
5.1.34 Menu: Communication
Menu/parameter
Value range
Description
HART Version
HART 5, HART 7
Use this parameter to define the HART protocol
via which the device is to communicate.
setting)
-
HART 5 - HART Protocol 5.9
-
HART 7 - HART Protocol 7.2 (factory
Note:
-
If the HART 7 function ‘Write protection
(Lock ALL)’ has been activated via the DTM/
EDD and communication has been switched
to HART 5 on the device, write protection is
canceled when the device is restarted.
-
In the event of a switch from HART 7 to HART
5, if write protection has been activated via
HART 7, it is deactivated when the device is
restarted.
-
When switching from HART 5 to HART 7,
device addresses greater than number 15 are
set to 0.
Find Device*
Off*
Find Once*
Find Continuous*
If ‘Find Once’ is selected, after HART command
#73 is received the device responds once with
HART command #73, which has the same content
as command #0.
If ‘Find Continuous’ is selected - after HART
Command #73 is received, the device responds
recurrently with HART Command #73, which has
the same content as Command #0.
Selecting the ‘Off’ parameter ends the ‘Find
Device’ function.
* Parameter only visible if HART 7 has been selected.
Содержание SP8-10
Страница 8: ...IM P707 01 CTLS Issue 1 8 SP8 10 Smart positioner Label example ...
Страница 51: ...IM P707 01 CTLS Issue 1 51 SP8 10 Smart positioner Fig 28 Continued on next page ...
Страница 52: ...IM P707 01 CTLS Issue 1 52 SP8 10 Smart positioner Fig 29 Continued on next page ...
Страница 53: ...IM P707 01 CTLS Issue 1 53 SP8 10 Smart positioner Fig 30 ...
Страница 85: ...IM P707 01 CTLS Issue 1 85 SP8 10 Smart positioner 7 Maintenance Spares available SP8 Series filter kit ...
Страница 86: ...IM P707 01 CTLS Issue 1 86 SP8 10 Smart positioner ...
Страница 87: ...IM P707 01 CTLS Issue 1 87 SP8 10 Smart positioner ...
Страница 88: ...IM P707 01 CTLS Issue 1 88 SP8 10 Smart positioner ...