SP8-10 Smart positioner
5.1.33 Menu: Universal input
Menu/parameter
Value range
Description
UI SP Value Max.
4.0 to 20.0 mA
Use this parameter to specify the upper current range
limit for the universal input.
UI SP Value Min.
4.0 to 20.0 mA
Use this parameter to specify the lower current range
limit for the universal input.
UI Damping
0 to 60 s
Use this parameter to set a damping value for the
universal input signal.
UI Charact.
Linear, Custom
Use this parameter to select a function that adjusts the
behavior of the positioner to the Analogue input signal
according to a predefined course.
This linearizes the characteristic curves for the valves
and fittings and improves the behavior of the overall
control loop.
-
Linear - linear
-
Custom - configurable by user
The user-configurable characteristic curve cannot be
generated and saved in the device locally, however;
this can only be done via a PC with the appropriate
configuration program (DTM/EDD).
UI Out Value Min
0.0 to 30000
Use this parameter to define which value is assigned to
the minimum universal input signal ‘UI SP Value Min.’.
UI Out Value Max
0.0 to 30000
Use this parameter to define which value is assigned to
the maximum universal input signal ‘UI SP Value Max.’.
Содержание SP8-10
Страница 8: ...IM P707 01 CTLS Issue 1 8 SP8 10 Smart positioner Label example ...
Страница 51: ...IM P707 01 CTLS Issue 1 51 SP8 10 Smart positioner Fig 28 Continued on next page ...
Страница 52: ...IM P707 01 CTLS Issue 1 52 SP8 10 Smart positioner Fig 29 Continued on next page ...
Страница 53: ...IM P707 01 CTLS Issue 1 53 SP8 10 Smart positioner Fig 30 ...
Страница 85: ...IM P707 01 CTLS Issue 1 85 SP8 10 Smart positioner 7 Maintenance Spares available SP8 Series filter kit ...
Страница 86: ...IM P707 01 CTLS Issue 1 86 SP8 10 Smart positioner ...
Страница 87: ...IM P707 01 CTLS Issue 1 87 SP8 10 Smart positioner ...
Страница 88: ...IM P707 01 CTLS Issue 1 88 SP8 10 Smart positioner ...