IM-P707-01
CTLS Issue 1
78
SP8-10 Smart positioner
5.1.40 Menu: Service
(continued)
Menu/parameter
Value range
Description
Sensor Calib.*
Value 1 ... Value 5
Confirm
Once the position sensor has been replaced, the
correction values used for linearizing the sensor
characteristic curve (supplied by the factory together
with the position sensor) can be entered here.
The entered values are accepted by using ‘
Confirm
’.
Sensor Position
0° Position
Use this parameter to set the fine adjustment of the 0°
position after a sensor replacement.
The current position of the sensor range is accepted as
a center position by using ‘
Confirm
’.
AO Alarm Current*
Low, High
Use this parameter to set the alarm current for the
Analogue position feedback. This current is output
even if the positioner is in a no-current state (external
supply).
-
High - I > 21.5 mA
-
Low - I < 3.6 mA
*Parameter is only visible if Service Mode is set to ‘On’.
Содержание SP8-10
Страница 8: ...IM P707 01 CTLS Issue 1 8 SP8 10 Smart positioner Label example ...
Страница 51: ...IM P707 01 CTLS Issue 1 51 SP8 10 Smart positioner Fig 28 Continued on next page ...
Страница 52: ...IM P707 01 CTLS Issue 1 52 SP8 10 Smart positioner Fig 29 Continued on next page ...
Страница 53: ...IM P707 01 CTLS Issue 1 53 SP8 10 Smart positioner Fig 30 ...
Страница 85: ...IM P707 01 CTLS Issue 1 85 SP8 10 Smart positioner 7 Maintenance Spares available SP8 Series filter kit ...
Страница 86: ...IM P707 01 CTLS Issue 1 86 SP8 10 Smart positioner ...
Страница 87: ...IM P707 01 CTLS Issue 1 87 SP8 10 Smart positioner ...
Страница 88: ...IM P707 01 CTLS Issue 1 88 SP8 10 Smart positioner ...