IM-P707-01
CTLS Issue 1
46
SP8-10 Smart positioner
5.1.9 Start automatic adjustment
The Auto Adjust function of the device can be configured and started in the ‘Operating mode’ menu.
1.
Use
RIGHT
to switch to the operating mode menu
2.
Use
UP
or
DOWN
to select the ‘Adaptive’ operating mode.
3.
Confirm the selection with RIGHT. Press and hold down the
control button for at least 4 seconds (wait for the time to count
down on the top left of the display).
4.
Use
UP
or
DOWN
to select ‘Actuator type’.
Select ‘Rotary’ for rotary actuators.
Select ‘Linear’ for linear actuators.
5.1.10 Switching the operating mode
Note:
The ‘Auto adjust Mode’ can be pre-set at the configuration level in ‘.../Easy Setup/Auto adjust Mode’.
The progress of the Auto Adjust function is shown in a bar graph. The function can be terminated with
‘Abort’ if necessary. Once Auto Adjust has been completed successfully, ‘Auto Adjust Complete’ is
displayed. The device then switches to the process display automatically.
Note:
Auto Adjust does not always result in optimum control conditions.
When Auto Adjust is started via shortcut keys, the position of the valve is determined automatically.
Содержание SP8-10
Страница 8: ...IM P707 01 CTLS Issue 1 8 SP8 10 Smart positioner Label example ...
Страница 51: ...IM P707 01 CTLS Issue 1 51 SP8 10 Smart positioner Fig 28 Continued on next page ...
Страница 52: ...IM P707 01 CTLS Issue 1 52 SP8 10 Smart positioner Fig 29 Continued on next page ...
Страница 53: ...IM P707 01 CTLS Issue 1 53 SP8 10 Smart positioner Fig 30 ...
Страница 85: ...IM P707 01 CTLS Issue 1 85 SP8 10 Smart positioner 7 Maintenance Spares available SP8 Series filter kit ...
Страница 86: ...IM P707 01 CTLS Issue 1 86 SP8 10 Smart positioner ...
Страница 87: ...IM P707 01 CTLS Issue 1 87 SP8 10 Smart positioner ...
Страница 88: ...IM P707 01 CTLS Issue 1 88 SP8 10 Smart positioner ...