Example 2: three-step
-
set the POWER START 1 = 20% START POWER 2 = 30%, START POWER 3 = 50%,
START TIME 1 = 3s, START TIME 2 = 3s, START TIME 3 = 3s, MAX POWER = 100%. This means that the rotor
starts with 20% power, within 3 s power reaches 30%, followed by 3s power reaches 50% and last 3 s power up
to 100%.
STOP POWER, STOP TIME
Use, if we want to obtain a so-called soft stop. It works the same way as soft start so that the other
way.
STOP AT
Specifies how many degrees before the specified angle (for example, sent by a computer program like
Orbitron) is to start the motor stopping. It matters if it is selected in the parameter mode STOP softly module
MOTOR CONFIGURATION.
PULS TIMEOUT
Specifies how long the motor has run off its power, if it does not come from the motion sensor pulses.
Applies only to motors of type
DIGITAL
.
SET COM 0, SET COM 1
STATE
Read only. Possible values: ON or OFF.
BAUD
Possible values: 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 230400 and 460800.