Chapter 5: Programming Examples
5-3
User’s Manual Pub. 0300181-07 Rev. A
Channel 0 Output Register Configuration (O:e.0)
Config. Bit
Description
Bit Setting
Description
*15
Normal
0
Normal Mode
14
Roll Under
1
Preset
13
Roll Over
0
Roll to Zero
12
Direction
0 (Default)
No Inversion
11
Count Size
0 (Default)
±32K
10
Freq. Filter
0 (Default)
50kHz
9
Stop on Limit
0
No Stop
8
Stop on Zero
0 (Default)
N/A
6/7
Count Mode
00 (Default)
Uni-Directional
4/5
Input Range
00 (Default)
50mV-30VAC
3
Rate Mode
0 (Default)
Instant
2
Reset Flags
0 (Default)
Toggle each Rev.
1
Counter Preset
0 (Default)
Off
Output Word - O:e.1 Counter Preset= 20,000
Output Word - O:e.2 Counter Limit = 20,000
A ring counter is configured by setting the preset and limit values to the same
count and setting the roll over to zero and roll under to preset bits. Zero must
always be the starting point and the maximum value must always be positive.
The above figure illustrates counting in a clockwise direction.
Section 5.4 Using
Preset Values with
Extended Mode
The Counter Preset and Counter Limit functions are affected by the Count Size
Configuration Bit 11. The default counter range is ±32 K but may be extended to
±8 M.
When operating in the extended range, ±8 M, all Counter Preset and Counter
Содержание SLC 500
Страница 1: ...User s Manual Pub 0300181 07 Rev A ...
Страница 8: ...viii SLC 500 50 kHz Counter Flowmeter Input Module User s Manual Pub 0300181 07 Rev A ...
Страница 24: ...2 10 Chapter 2 Installation and Wiring User s Manual Pub 0300181 07 Rev A ...
Страница 55: ...Chapter 6 Testing Your Module 6 5 User s Manual Pub 0300181 07 Rev A ...
Страница 56: ...6 6 Chapter 6 Testing Your Module User s Manual Pub 0300181 07 Rev A ...
Страница 60: ...7 4 Chapter 7 Maintaining your Module and Ensuring Safety User s Manual Pub 0300181 07 Rev A ...
Страница 64: ...A 4 Appendix A Floating Point Rate Mode User s Manual Pub 0300181 07 Rev A ...
Страница 65: ...User s Manual Pub 0300181 07 Rev A ...