5-6
Chapter 5: Programming Examples
User’s Manual Pub. 0300181-07 Rev. A
Channel
Register
5
I:e.23
6
I:e.27
7
I:e.31
Clearing Loaded Factor Data
In order to clear the factored data 0 must be loaded into the Preset / K Factor,
Limit / M Factor and Limit / R Factor registers. After entering 0 into these
registers bit 15 of the module Configuration register must be toggled from 0 to 1
and then back to 0.
There are 4 registers assigned for each Channels output configuration word. The
first register assigned is the channel configuration register. The next 3 registers
are the Preset/K Factor, Limit /M Factor and Limit/R Factor registers
respectively.
Refer to Chapter 3 for detailed information regarding the output configuration
registers and their functions.