Chapter 4: Channel Configuration, Data, and Status
4-5
User’s Manual Pub. 0300181-07 Rev. A
Frequency Error
Frequency Error
Figure 4-3. One Period Rate Measurement
The accuracy while operating in the average mode is ±1 count. When using the
Instant mode, the accuracy is ±1% at 50 kHz and improves to
±0.002% at 100
Hz. The graph below shows the rate accuracy in Hertz vs. Frequency.
Input Range: (Configuration Bits 4-5)
This group of 2 bits selects one of 4 input ranges. Each range is selected for a
given system voltage level. Each range has its own counter trip level. Refer to the
Specifications section of this manual for input limit information.
Table 4-2. Input Range Selection Bits
Mode
Bit Setting
Range
AC
00
50 mV to 30 VAC
DC
01
0 to 5 VDC
DC
10
0 to 12 VDC
DC
11
0 to 24 VDC
NOTE
The input range must configured in channel pairs to operate properly.
Pairs are channels 0-1, 2-3, 4-5, 6-7.
NOTE
You should allow at least 1 scan time for input range information to be
updated at the PLC.
E
rro
r in
Hz
Содержание SLC 500
Страница 1: ...User s Manual Pub 0300181 07 Rev A ...
Страница 8: ...viii SLC 500 50 kHz Counter Flowmeter Input Module User s Manual Pub 0300181 07 Rev A ...
Страница 24: ...2 10 Chapter 2 Installation and Wiring User s Manual Pub 0300181 07 Rev A ...
Страница 55: ...Chapter 6 Testing Your Module 6 5 User s Manual Pub 0300181 07 Rev A ...
Страница 56: ...6 6 Chapter 6 Testing Your Module User s Manual Pub 0300181 07 Rev A ...
Страница 60: ...7 4 Chapter 7 Maintaining your Module and Ensuring Safety User s Manual Pub 0300181 07 Rev A ...
Страница 64: ...A 4 Appendix A Floating Point Rate Mode User s Manual Pub 0300181 07 Rev A ...
Страница 65: ...User s Manual Pub 0300181 07 Rev A ...