Product Overview
TM40/40UFI Rev. (Ai), February 2019
21
2.4.5.3
SIL-2
The 40/40UFI Flame Detector is approved per SIL-2 requirement per IEC
61508.4, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
•
Alert signal via 0
–
20mA current loop
Or
•
Alert signal via alarm relay and fault relay
•
For more details and guidelines for configuring, installing, operating, and
service, see
on page 79 and
TÜV Report No. 968/EZ 348.
2.4.5.4
EN54-10
The 40/40UFI Flame Detector is approved per EN54-10 and CPD.
•
The detector is listed as Class 1 for sensitivity settings 30, 45 and 60, and
Class 2 for sensitivity settings 15, 30, 45, 60.
•
The detector is approved per EN54-10 by VdS.
•
This test includes a functional test, environmental test, EMI/EMC test, and
software check.
•
For more details see VdS Report No. BMA 150190-AU01+BZA02-PB01.
2.4.5.5
Inmetro (UL)
The 40/40UFI Flame Detector is in compliance with the standards ABNT NBR IEC
60079-0, ABNT NBR IEC 60079-1, ABNT NBR IEC 60079-7, ABNT NBR IEC
60079-18, ABNT NBR IEC 60079-31, and INMETRO decree No. 179 as of May
18th, 2010. Further details may be found on Certificate of Compliance No. UL-BR
16.065XX.
2.4.5.6
TR CU/EAC
The 40/40UFI Flame Detector is in compliance with the standard TR CU 012/2011
per:
1 Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T96°C Db X
(
–55°C ≤ Ta ≤ +75°C)
Or
1 Ex db eb op is IIC T4 Gb X
Ex tb op is IIIC T106°C Db X
(
–55°C ≤ Ta ≤ +85°C)
Or
1 Ex db eb mb op is IIC T4 Gb X
Ex tb op is IIIC T98°C Db X