Accessories
70
SharpEye™
Ultra-Fast IR3 Flame Detector User Guide
D.1.2
Unpacking
Verify that you have received the following contents:
•
Delivery form
•
Flame simulator with integral battery
•
Tool keys
•
User manual
•
FAT forms
•
EU declaration
•
Storage case
D.1.3
Operating Instructions
Warning:
Do not open the flame simulator to charge the batteries or for any
other reason in a hazardous area.
Caution:
The following test simulates a real fire condition and may activate the
extinguishing system or other alarms. If activation is not desired,
disconnect/inhibit them before the test and reconnect after the
simulation.
To simulate a fire:
Verify you are at the correct distance from the detector according to the type
of detector and the detector sensitivity.
Using the mechanical sight, aim the flame simulator toward the center of the
detector.
Push the activate button, and then use the laser spot for fine adjustment
toward the center of the detector.
Keep the simulator aimed at the detector for up to 50 seconds, until you
trigger an alarm.
Wait 20 seconds before repeating the test.