Accessories
TM40/40UFI Rev. (Ai), February 2019
71
D.1.4
Range
Table 26: Sensitivity Ranges
Sensitivity
Detection Range (ft/m)
Standard Test Range (ft/m)
1 (Low)
66/20
13/4
2
133/40
26/8
3
200/60
40/12
4 (High)
300/90
50/15
Notes:
•
The minimum distance from the detector is 20
”/
50cm.
•
At extreme temperatures, there is a 15% maximum reduction in
the range.
Warning:
Keep the flame simulator in a safe place when not in use.
D.1.5
Charging the Battery
The flame simulator uses lithium-ion batteries as a rechargeable power source.
When the batteries are fully charged, the simulator operates at least 1,000 times
without having to be recharged. The simulator will not operate when the voltage
from the batteries is lower than the required operational level.
1
Simulator
3
Locking Disc
2
Battery Pack
4
Back Cover
Figure 15: Flame Simulator Battery Replacement