General Instructions for Electrical Wiring
66
SafEye
TM
Xenon 700S Gas Detector User Guide
Table 23: Wiring Length in Feet/Meters
No. of
Detectors
Recommended Wire Diameter
Power Supply Range
(VDC)
24
18
16
14
-
-
22–32
20
18
16
14
-
-
22–32
16
20
18
16
14
-
22–32
12
20
18
16
14
-
20–32
8
20
18
16
14
-
20–32
4 and less
20
18
16
16
14
20–32
ft
164
328
492
656
820
meters
50
100
150
200
250
Max. Length from power supply to last
detector