Output Signals
32
SafEye
TM
Xenon 700S Gas Detector User Guide
Table 6: Optional - Discrete Reading of 0–20mA at Different Detector
Modes
Current Reading Status and Description
LEL.m
Setting
0+0.3mA
Fault 2 or Low Voltage
-
1±0.3mA
Zero Calibration
-
2±0.3mA
Fault 1
-
3±0.3mA
“Maintenance Call”
-
4±0.5mA
Standby
-
14±0.5mA
Warning
1
19±0.5mA
Alarm
3
21mA
Concentration is over the range limit
(more than full-scale concentration)
3.2.2
Dry Contact Relays
The detector may include up to 3 of the following relays depending on the
wiring configuration:
Fault relay
Alarm relay
Accessory relay
Alarm and accessory relays are normally non-energized open. When the
detector is in alarm or warning status, the appropriate relay is closed.
Fault relay is normally energized closed, and when it is in the fault
condition, the relay is opened.
3.2.3
RS-485 Interface
The detector has an RS-485 Modbus-compatible input/output that can send
data communication to a PC loaded with the appropriate host software, and
receive data or control commands from the PC.