Page 3-8
Switch 6 12 or 24-hour Display
Switch 6 12 or 24-hour Display
Switch 6 12 or 24-hour Display
Switch 6 12 or 24-hour Display
Switch 6 12 or 24-hour Display
T
his switch configures the TimeView 400 display for 12-
or 24-hour time format. To display time in a 12-hour
format, place this switch in the ON position.
Placing this switch in the OFF position configures the
display for 24-hour time format.
Switch 7 Synchronization Source
Switch 7 Synchronization Source
Switch 7 Synchronization Source
Switch 7 Synchronization Source
Switch 7 Synchronization Source
This switch configures the clock for operation from a
NetClock Master Clock or computer synchronization
source. Place this switch in the OFF position when the
clock is connected to a NetClock or TimeBridge.
For computer set applications, place this switch in the ON
position.
Switch 8 and 9 Reserved
Switch 8 and 9 Reserved
Switch 8 and 9 Reserved
Switch 8 and 9 Reserved
Switch 8 and 9 Reserved
DIP switches 8 and 9 are reserved for test functions. To
ensure proper operation, place these switches in the OFF
position.
Switch 10 Termination
Switch 10 Termination
Switch 10 Termination
Switch 10 Termination
Switch 10 Termination
This switch terminates the RS-485 data bus into 120
ohms. Place this switch in the ON position when the clock
is installed at the end of the RS-485 data bus. Otherwise,
place this switch in the OFF position.