Page 12 of 24
4.2
SRP30 Hi/Lo
(Direct Burner Spark Ignition)
4.2.1
The appliance should be raised and suspended from chains or drop rods, or from brackets fixed to vertical
surfaces that have been previously installed in accordance with Section 3.1. - Suspension.
4.2.2
Connect the gas supply in accordance with Section 3.2. - Gas supply, of these Installation Instructions.
4.2.3
Using three core and earth flexible supply cable as specified in section 3.3.3, suitable for 230v ~ 50Hz 25W
supply, connect the 4 pin electrical socket provided (fitted to junction box, attached to the Control valve) as
follows:-
Brown
-
to terminal marked 1
Blue
-
to terminal marked 2
Black
-
to terminal marked 3
Green/Yellow
-
to terminal marked
7
External fuse required - 3 amp
See Section 3.3 for electrical supply requirements.
4.3
SRP08/SRP15/SRP22 (Standing Pilot Ignition)
4.3.1
The appliance should be raised and suspended from chains or drop rods, or from brackets fixed to a
vertical surface which have been previously installed in accordance with Section 3.1 suspension.
4.3.2
Connect the gas supply in accordance with Section 3.2 - Gas Supply, of these Installation Instructions.
4.3.3
IMPORTANT:
THIS APPLIANCE MUST NOT BE CONNECTED TO ANY ELECTRICAL SUPPLY.
The appliance may be controlled via a 2 pole switch and/or a thermostat, connected by 2 core flexible supply
cable (suitable for millivolt electrical supply) to the appliance control valve connections marked TH
(see Fig. 9).
Fig. 9
ROOM
THERMOSTAT
TP = MILLIVOLT GENERATOR
TH = SWITCH / THERMOSTAT
AUTOMATIC SHUT-OFF VALVE
POWERED BY MILLIVOLT GENERATOR