Multiple Heater Horizontal Venting Arrangement
VENT SIZING TABLE
—
Multiple Heater Venting
Number of Heaters
Horizontal and vertical
Vertical Only
1
2
3
4
PGR 40
4”
4”
4”
4”
PGR 50
4”
4”
4”
5”
PGR 60
4”
4”
4”
5”
PGR 75
4”
4”
5”
6”
COMMON VENT DIAMETER