Amount counting : time factor for each
digital input.
The electrical device is not connected
to an electricity meter.
In this case, knowing the electrical
power of this device, it is possible to
integrate its power over the time or to
define in Wh the consumption of
electrical energy.
The pulse factor « Ax factor » must be
defined according to the unit Wh.
Example: A pump of 400W switched on
during 1 hour consumes an electrical
energy of 400Wh.
The factor (Ax factor) will be configured
with 400 [Wh]/3600 [sec] = 0.111.
The counting can be by open or close
contact.
Inputs A1 and A2
Inputs A1-A2 only allow “Binary
Counting” and are controlled under the
menu point “Inputs/Outputs”.
The inputs can be configured in the
long (<=5 Hz) or fast (>5 Hz) mode.