11 Troubleshooting
When the PV system does not operate normally, we recommend
the following solutions for quick troubleshooting. If an error
occurs, the red LED will light up. There will have “Event
Messages" display in the monitor tools. The corresponding
corrective measures are as follows:
Object
Error
code Corrective measures
Presumable
Fault
E33
• Check the grid frequency and observe
how often major fluctuations occur.
If this fault is caused by frequent
fluctuations, try to modify the operating
parameters after informing the grid
operator first.
E34
• Check the grid voltage and grid
connection on inverter.
• Check the grid voltage at the point of
connection of inverter.
If the grid voltage is outside the