UM0005_ASW 8-20K-LT-G2_EN_V03_1121 23
Object Description
Value
A
External diameter
10…16 mm
B
Conductor cross-section
2.5…6 mm
2
C
Stripping length of the insulated
conductors
Approx. 13
mm
D
Stripping length of the AC cable’s
outer sheath
Approx.53 mm
The PE insulated conductor must be 2 mm longer than the L
and N conductors
Larger cross-sections should be used for longer leads.
Cable Design
The conductor cross-section should be dimensioned to avoid
power loss in cables exceeding 1% of rated output power.
The required conductor cross-section depends on the inverter
rating, ambient temperature, routing method, cable type, cable
losses, valid installation requirements of installation side.
Residual current protection
The product is equipped with an integrated universal current-
sensitive residual current monitoring unit inside. The inverter will
disconnect immediately from the mains power as soon as fault
current with a value exceeding the limit.