18
4
Setting
voltage point
back to
battery mode
when
selecting
"SBU priority"
or "Solar first"
in program 2.
Options in POWERBACK PB1000S model:
Full/12.5V/13V/13.5V(default)/14.0V
Options in POWERBACK PB2000S model:
Full/25V/25.5V/26V/26.5V/27V(default)/27.
5V/28V.
5
Setting
voltage point
back to utility
source when
selecting
"SBU priority"
or "Solar first"
in program 2.
Options in POWERBACK PB1000S model:
10.5V/11.0V(default)/11.5V/12.0V
Options in POWERBACK PB2000S model:
21V/21.5V/22V(default)/22.5V/
23V/23.5V/24V/24.5V.
6
Max charging
current:
To configure
total charging
current for
solar and
utility
chargers:
(Max.
charging
current=utility
charging
csolar
charging
current)
Options in POWERBACK PB1000S model:
20A/30A/40/50A/60A(default)/70A/80A
Options in POWERBACK PB2000S model:
20A/30A/40/50A/60A(default)/75A
7
Max utility
charging
current
Options in POWERBACK PB1000S model:
0A/5A/10A/15A/20A (default)
Options in POWERBACK PB2000S model:
0A/5A/10A/15A (default)
8
Auto restart
when
overload
occurs
Restart disable(default):
when unit is overload, unit will release
overload alarm, then turn off output &
release fault alarm, unit won’t restart again
until end-user reduce load & press unit’s
on/off power switch.
Restart enable:
When unit is overload, overload alarm 5
seconds and turn off output for 15 seconds,
then restart unit again. The restart cycle is 5
times.