To prevent overheating, be sure that the inverter has adequate air flow around it. A minimum
clearance of 300mm (12 in) should be kept between inverter & other equipment & 500mm
(20 in) of clearance between the bottom of the inverter and the ground.
Visibility of the LED indicator lights should be considered. Ideally, the indicator light should
be at eye-level.
Adequate ventilation around the inverter must be provided.
NOTE
Nothing should be stored on top of or placed against the inverter.
The inverter must be mounted vertically with a maximum incline of +/- 5 degree.
Exceeding this may cause the output power to derate.
Figure 4.5 Inverter Mounting Clearances
Mount the inverter on a wall or structure capable of bearing the weight of the machine
300mm
(12 in)
300mm
(12 in)
300mm
(12 in)
300mm
(12 in)
300mm
(12 in)
500mm
(20 in)
500mm
(20 in)
4. Installation
13
4.3 Mounting the Inverter
When the inverter is mounted on the wall, it sticks out approximately 9.5 inches.
Keep this in mind when selecting the installation location for the inverter.